Specifications: Electrical Specification

CAUTION!

AC and DC disconnect switches and over-current protection must be included in the installation.

All wiring must comply with all applicable national and/or local electrical codes.

Note

Max. prospective RMS short-circuit current on input terminals: 200 kA

Max. prospective RMS short-circuit current on battery terminals: 50 kA

Note

AC Input

AC Input

Input Rating

1000 kW/kVA

Power Factor

1

Input Voltage

480 V

Input Frequency

60 Hz

Nominal Input Current (note 1)

1240 A

Maximum Input Current (note 2)

1364 A

Input Current Limitation (note 3)

1564 A

Recommended Cable per phase (notes 4, 6, 7, a, b, c)

5 × 500 kcmil

 

 

DC Input

DC Input

Nominal Voltage (note 5)

2 x 384 V

INom Discharge (note 8)

1356 A

IMax Discharge (note 9)

1595 A

Recommended cable (per pole)

5 × 500 kcmil

CAUTION!

The minimum DC voltage rating of the battery supply over-current protective device is 500 V.

30

Symmetra MW 1000 kW 480 V Installation - 990-4112E

Page 34
Image 34