| Electrical Installation: Bypass Static Switch Wiring | ||||||||
Top cable entry |
|
|
|
|
|
|
|
|
|
Top view of top cable entry |
|
| Top view of AC IN & OUT cable | ||||||
|
|
| connections | ||||||
| |
|
|
|
|
|
|
|
|
|
|
|
|
|
| ||||
|
|
|
|
|
|
|
| ||
|
|
|
|
|
|
|
|
|
|
L1 IN | L1 OUT | L2 IN | L2 OUT | L3 IN | L3 OUT |
| | PE |
| | | |
|
|
|
|
|
|
| UPS Summary |
|
|
Port for communication cables |
|
|
| ~ | ~ |
|
| L1 IN | L2 IN | L3 IN |
|
| |
| L1 OUT | L2 OUT | L3 OUT |
| ||
|
| | | | | |
|
|
|
1.75 in / | 1.75 in / | |
44.45 mm | ||
44.45 mm | ||
| ||
| 2.3 in / 58 mm |
Loosen the 8 bolts to remove top cover.
No drilling or cutting should take place over the top of the UPS.
Note
Drill holes for conduits.
Feed cables through conduits. Connect cables at cable connection points as illustrated.
Connect grounding electrode conductor to busbar locations as shown.
Symmetra MW 1000 kW 480 V Installation - | 19 |