PARAMETER NAME/

DESCRIPTION

DISPLAY SCREENS /

[MENU LOCATION]

 

DEFAULT SETTINGS

 

 

 

 

 

 

 

Firmware Version

Version number of the control unit

FW Version

+

{Status Only}

firmware.

000189

[SYSTEM/SETUP]

NOTE: Actual firmware version

 

 

 

number displayed is the current

 

 

 

version as of the date of manufacture.

 

 

 

This parameter cannot be changed.

 

 

GMT 1 Alias

An alternate name (alias) that can be

GMT 1

m+

Security Level {1}

assigned to a GMT Fuse 1 if desired.

-48V

 

[MODULES/GMT/ALIAS]

 

 

 

 

 

 

GMT 8 Alias

An alternate name (alias) that can be

 

Security Level {1}

assigned to a GMT Fuse 8 if desired.

GMT 8

m+

[MODULES/GMT/ALIAS]

 

-48V

 

 

 

 

GMT 1 Blown

The Output Relay that is energized when

GMT 1 Alm

m+

Security Level {1}

GMT Fuse 1 is blown.

Major

[MODULES/GMT/SET-ALM]

 

 

 

 

 

 

GMT 8 Blown

The Output Relay that is energized when

 

Security Level {1}

GMT Fuse 8 is blown.

GMT 8 Alm

m+

[MODULES/GMT/SET-ALM]

 

Major

 

 

Hardware Battery Current

The output relay energized if there is a

Hw Batt C Almm+

Alarm

hardware failure in the battery current

Minor

Security Level {2}

monitoring function.

 

 

[SYSTEM/SET-ALM]

 

 

 

Hardware Battery Temperature

The output relay energized if there is a

Hw Batt T Almm+

Alarm

hardware failure in the battery

Minor

Security Level {2}

temperature monitoring function.

 

 

[SYSTEM/SET-ALM]

 

 

 

Hardware LVD Alarm

The output relay energized if there is a

Hw LVD Alm

m+

Security Level {2}

conflict between the commanded and

Minor

[SYSTEM/SET-ALM]

sensed positions of the LVD contactor.

 

 

 

Generally the contactor is open when it

 

 

 

should be closed.

 

 

Hardware System Temperature

The output relay energized if there is a

Hw Sys T Alm m+

Alarm

hardware failure in the system

Minor

Security Level {2}

temperature monitoring function.

 

 

[SYSTEM/SET-ALM]

 

 

 

Hardware System Voltage

The output relay energized if there is a

Hw Sys V Alm m+

Alarm

hardware failure in the system voltage

Minor

Security Level {2}

monitoring function.

 

 

[SYSTEM/SET-ALM]

 

 

 

MX28B200/400 –48 VDC User’s Manual (990-9133)

Page 31

Page 37
Image 37
American Power Conversion MX28B200 FW Version, 000189, GMT 1 Alm, GMT 8 Alm, Hw Batt C Almm+, Hw Batt T Almm+, Hw LVD Alm