PARAMETER NAME/

DESCRIPTION

DISPLAY SCREENS /

[MENU LOCATION]

 

DEFAULT SETTINGS

 

 

 

 

 

 

 

Circuit Breaker 1 Alias

An alternate name (alias) that can be

Cir Bkr 1

m+

Security Level {1}

assigned to a circuit breaker if desired.

 

-48V

[MODULES/CIRBKR/ALIAS]

 

 

 

 

 

 

Circuit Breaker 24 Alias

An alternate name (alias) that can be

 

Security Level {1}

assigned to a circuit breaker if desired.

Cir Bkr 24

m+

[MODULES/CIRBKR/ALIAS]

 

 

-48V

 

 

 

Circuit Breaker 1 Tripped

An alarm that indicates Circuit Breaker 1

Cir Bkr 1 Alm m+

Security Level {1}

is tripped.

Major

[MODULES/CIRBKR/SET-

 

 

 

ALM]

 

 

 

 

 

 

Circuit Breaker 24 Tripped

An alarm that indicates Circuit Breaker

 

Security Level {1}

24 is tripped.

Cir Bkr 24 Almm+

[MODULES/CIRBKR/SET-

 

 

Major

ALM]

 

Compensation High Knee

The temperature compensation high

Comp Hknee

m+

Security Level {1}

knee is the point above which there is no

40.0 C

[BATT/COMP]

additional battery voltage compensation

 

 

 

for further increases in temperature.

 

 

Compensation Low Knee

The temperature compensation low knee

Comp Lknee

m+

Security Level {1}

is the point below which there is no

 

0.0 C

[BATT/COMP]

additional battery voltage compensation

 

 

 

for further decreases in temperature.

 

 

Compensation Method

One of three parameters that control the

Comp Method m+

Security Level {1}

DC output voltage. Activate “ON” or de-

 

OFF

[BATT/COMP]

activate “OFF” battery temperature

 

 

 

compensation.

 

 

Compensation Temperature

Temperature compensation coefficient

Comp TC

m+

Coefficient

between low knee and high knee in

-

3.00mV

Security Level {1}

mV/cell/°C. (Compensation equals zero

 

 

[BATT/COMP]

at 25°C.)

 

 

Control Unit Revision

Hardware revision level of the control

Cntrl Rev

+

{Status Only}

unit. This parameter cannot be changed.

000002

[SYSTEM/SETUP]

 

 

 

Date

Internal system calendar date. Used as

Date

m+

Security Level {1}

a date stamp in the event log.

DEC 16 1999

[SYSTEM/DATE]

 

 

 

Display Type

Type number for the control unit display.

Display Type +

{Status Only}

This parameter cannot be changed.

000255

[SYSTEM/SETUP]

 

 

 

Fahrenheit Scale

Enables selection of Fahrenheit or

Fahrenheit

m+

Security Level {1}

Celsius temperature scale (Fahrenheit

 

OFF

[SYSTEM/SETUP]

“OFF” displays readings in °C).

 

 

Page 30

MX28B200/400 –48 VDC User’s Manual (990-9133)

Page 36
Image 36