PARAMETER NAME/  | DESCRIPTION  | DISPLAY SCREENS /  | |
[MENU LOCATION]  | 
  | DEFAULT SETTINGS  | |
  | 
  | 
  | |
  | 
  | 
  | |
Battery Discharge Alarm  | The output relay energized if the battery  | Batt Disc Alm m+ | |
Security Level {1}  | discharge current exceeds the  | Minor | |
 | programmed battery discharge threshold.  | 
  | 
  | 
Battery Discharge Threshold  | An alarm is generated if the battery  | Batt Disc Thr m+ | |
Security Level {1}  | discharge current exceeds this value.  | 
  | 10 A | 
  | 
  | 
  | |
Battery Float Voltage  | One of three parameters that control the  | Batt Float | m+  | 
Security Level {1}  | DC output voltage. Set the Float Voltage  | 
 | |
[BATT/PARAM] | at 25°C battery temperature per the  | 
  | 
  | 
  | battery manufacturers recommendations.  | 
  | 
  | 
Battery High Temperature  | The output relay energized if the battery  | Batt HT Alm  | m+  | 
Alarm  | temperature exceeds the Battery High  | Minor  | |
Security Level {1}  | Temperature threshold.  | 
  | 
  | 
  | 
  | 
  | |
Battery High Temperature  | Battery Temperature is temperature  | Batt HT Thr  | m+  | 
Threshold  | measured at the battery probe. An alarm  | 70.0 C | |
Security Level {1}  | is generated if the battery temperature  | 
  | 
  | 
exceeds this value.  | 
  | 
  | |
Battery High Voltage Alarm  | The output relay energized if the DC  | Batt HV Alm  | m+  | 
Security Level {1}  | output voltage rises above the battery  | Minor  | |
high voltage threshold.  | 
  | 
  | |
Battery High Voltage Threshold  | An alarm will be reported if temperature  | Batt HV Thr  | m+  | 
Security Level {1}  | is lower than the temperature entered.  | 
 | |
An alarm is generated if the DC output  | 
  | 
  | |
  | voltage rises above this value.  | 
  | 
  | 
Battery Low Temperature  | The output relay energized if the Battery  | Batt LT Alm  | m+  | 
Alarm  | Temperature drops below the battery  | Minor  | |
Security Level {1}  | Low Temperature threshold.  | 
  | 
  | 
  | 
  | 
  | |
Battery Low Temperature  | Battery Temperature is temperature  | Batt LT Thr | m+  | 
Threshold Security Level {1}  | measured at the battery probe. An alarm  | 
  | 0.0 C  | 
is generated if the battery temperature  | 
  | 
  | |
  | drops below this value.  | 
  | 
  | 
Battery Low Voltage Alarm  | The output relay energized if the DC  | Batt LV Alm  | m+  | 
Security Level {1}  | output voltage drops below the battery  | Minor  | |
low voltage threshold.  | 
  | 
  | |
Battery Low Voltage Threshold  | An alarm is generated if the DC output  | Batt LV Thr  | m+  | 
Security Level {1}  | voltage drops below this value.  | 
 | |
  | 
  | 
  | |
Battery Maximum Recharge  | One of three parameters that control the  | Batt Max Rechm+ | |
Current  | DC output voltage. If Battery Current  | 
  | 12 A | 
Security Level {1}  | surpasses the Maximum Battery  | 
  | 
  | 
[BATT/PARAM]  | Recharge Current, the DC output voltage  | 
  | 
  | 
  | will be reduced (the system limits the  | 
  | 
  | 
  | charging current to this programmable  | 
  | 
  | 
  | value).  | 
  | 
  | 
Battery Temperature  | Battery temperature measured by the  | Batt Temp | +  | 
{Status Only}  | system controller at the optional battery  | 25.2 C | |
[STATUS]  | temperature sensor probe.  | 
  | 
  | 
MX28B200/400   | Page 29  |