PARAMETER NAME/

DESCRIPTION

DISPLAY SCREENS /

[MENU LOCATION]

 

DEFAULT SETTINGS

 

 

 

 

 

 

 

PIN Entry

Screen for entry of the active password

PIN

m+

Security Level {0}

(PIN). Before any changes can be

 

0000

[PIN]

made, the correct pin for the desires

 

 

 

security level must be entered. Level 0 –

 

 

 

full read access. Level 1 –full read and

 

 

 

limited write access. Level 2 – full read

 

 

 

and write access.

 

 

Rectifier Communications Fail

The maximum rectifier communications

RectFailComm

m+

Timeout

response time allowed before a

1 min

Security Level {1}

communications failure is declared.

 

 

[MODULES/RECT/PARAM]

 

 

 

Rectifier Configuration Alarm

The output relay energized if the rectifier

Rect Cfg Alm

m+

Security Level {1}

configuration differs from its stored

Minor

[SYSTEM/SET-ALM]

configuration. This occurs if a rectifier is

 

 

 

added after configuration.

 

 

Rectifier Current Limit Alarm

The output relay that is energized or

Rect CL Alm

m+

Security Level {1}

special rectifier alarm group n of N that

n of N

[MODULES/RECT/SET-ALM]

occurs when a rectifier has been forced

 

 

 

into the current limited mode.

 

 

Rectifier Current Limit Alarm

The status will be “ON” if the rectifier has

Rect 1 CL

#

Status

been forced into its current limited mode.

OFF

{Status Only}

NOTE: This information can be

 

 

[MODULES/RECT/INFO]

viewed for each rectifier installed by

 

 

 

using the horizontal arrow keys.

 

 

Rectifier Current Output Status

A display of the DC output current for the

Rect 1 Curr

#

{Status Only}

individual rectifier. NOTE: This

24.9 A

[MODULES/RECT/INFO]

information can be viewed for each

 

 

 

rectifier installed by using the

 

 

 

horizontal arrow keys.

 

 

Rectifier Description

Displays the model number of the

Rect 1 Desc

#

{Status Only}

installed rectifier. NOTE: This

MRF28H54

 

[MODULES/RECT/INFO]

information can be viewed for each

 

 

 

rectifier installed by using the

 

 

 

horizontal arrow keys.

 

 

Rectifier Fail 1-of-N Alarm

The output relay energized if Rectifier

Rect 1ofN Almm+

Security Level {1}

Fail 1-of-N alarm occurs. This is a

Minor

[SYSTEM/SET-ALM]

special rectifier alarm group that signifies

 

 

 

that one rectifier has at least one alarm

 

 

 

condition.

 

 

Rectifier Fail 2-of-N Alarm

The output relay energized if Rectifier

Rect 2ofN Almm+

Security Level {1}

Fail 2-of-N alarm occurs This is a special

Major

[SYSTEM/SET-ALM]

rectifier alarm group that signifies that

 

 

 

more than one rectifier has at least one

 

 

 

alarm condition.

 

 

Rectifier Fail Safe Voltage

Rectifier default output voltage if

Rect Fail Safem+

Security Level {1}

communication with the control unit fails.

-54.00 V

[MODULES/RECT/PARAM]

 

 

 

Rectifier Fan Fail Alarm

The output relay that is energized or

Rect FF Alm

m+

Security Level {1}

special rectifier alarm group n of N that

n of N

[MODULES/RECT/SET-ALM]

occurs when a rectifier fan has failed.

 

 

Page 34

MX28B200/400 –48 VDC User’s Manual (990-9133)

Page 40
Image 40
American Power Conversion MX28B200 RectFailComm, Min, Rect Cfg Alm, Rect CL Alm, Rect 1 CL, Rect 1 Curr, 24.9 a, MRF28H54