PARAMETER NAME/  | DESCRIPTION  | DISPLAY SCREENS /  | |
[MENU LOCATION]  | 
  | DEFAULT SETTINGS  | |
  | 
  | 
  | |
  | 
  | 
  | 
  | 
PIN Entry  | Screen for entry of the active password  | PIN | m+  | 
Security Level {0}  | (PIN). Before any changes can be  | 
  | 0000 | 
[PIN] | made, the correct pin for the desires  | 
  | 
  | 
  | security level must be entered. Level 0 –  | 
  | 
  | 
  | full read access. Level 1   | 
  | 
  | 
  | limited write access. Level 2 – full read  | 
  | 
  | 
  | and write access.  | 
  | 
  | 
Rectifier Communications Fail  | The maximum rectifier communications  | RectFailComm | m+  | 
Timeout  | response time allowed before a  | 1 min | |
Security Level {1}  | communications failure is declared.  | 
  | 
  | 
[MODULES/RECT/PARAM]  | 
  | 
  | 
  | 
Rectifier Configuration Alarm  | The output relay energized if the rectifier  | Rect Cfg Alm | m+  | 
Security Level {1}  | configuration differs from its stored  | Minor | |
configuration. This occurs if a rectifier is  | 
  | 
  | |
  | added after configuration.  | 
  | 
  | 
Rectifier Current Limit Alarm  | The output relay that is energized or  | Rect CL Alm | m+  | 
Security Level {1}  | special rectifier alarm group n of N that  | n of N  | |
 | occurs when a rectifier has been forced  | 
  | 
  | 
  | into the current limited mode.  | 
  | 
  | 
Rectifier Current Limit Alarm  | The status will be “ON” if the rectifier has  | Rect 1 CL | #  | 
Status  | been forced into its current limited mode.  | OFF | |
{Status Only}  | NOTE: This information can be  | 
  | 
  | 
[MODULES/RECT/INFO] | viewed for each rectifier installed by  | 
  | 
  | 
  | using the horizontal arrow keys.  | 
  | 
  | 
Rectifier Current Output Status  | A display of the DC output current for the  | Rect 1 Curr | #  | 
{Status Only}  | individual rectifier. NOTE: This  | 24.9 A | |
[MODULES/RECT/INFO]  | information can be viewed for each  | 
  | 
  | 
  | rectifier installed by using the  | 
  | 
  | 
  | horizontal arrow keys.  | 
  | 
  | 
Rectifier Description  | Displays the model number of the  | Rect 1 Desc | #  | 
{Status Only}  | installed rectifier. NOTE: This  | MRF28H54 | 
  | 
[MODULES/RECT/INFO]  | information can be viewed for each  | 
  | 
  | 
  | rectifier installed by using the  | 
  | 
  | 
  | horizontal arrow keys.  | 
  | 
  | 
Rectifier Fail   | The output relay energized if Rectifier  | Rect 1ofN Almm+ | |
Security Level {1}  | Fail   | Minor | |
special rectifier alarm group that signifies  | 
  | 
  | |
  | that one rectifier has at least one alarm  | 
  | 
  | 
  | condition.  | 
  | 
  | 
Rectifier Fail   | The output relay energized if Rectifier  | Rect 2ofN Almm+ | |
Security Level {1}  | Fail   | Major | |
rectifier alarm group that signifies that  | 
  | 
  | |
  | more than one rectifier has at least one  | 
  | 
  | 
  | alarm condition.  | 
  | 
  | 
Rectifier Fail Safe Voltage  | Rectifier default output voltage if  | Rect Fail Safem+ | |
Security Level {1}  | communication with the control unit fails.  | 
 | |
[MODULES/RECT/PARAM]  | 
  | 
  | 
  | 
Rectifier Fan Fail Alarm  | The output relay that is energized or  | Rect FF Alm | m+  | 
Security Level {1}  | special rectifier alarm group n of N that  | n of N  | |
occurs when a rectifier fan has failed.  | 
  | 
  | |
Page 34  | MX28B200/400   | ||