American Power Conversion MX28B200 In-Rly 1 Alm, Ignore, In-Rly 4 Alm, Input Relay, Lamp Test

Models: MX28B200

1 61
Download 61 pages 5.27 Kb
Page 38
Image 38

PARAMETER NAME/

DESCRIPTION

DISPLAY SCREENS /

[MENU LOCATION]

 

DEFAULT SETTINGS

 

 

 

 

 

 

 

Input Relay 1

The Output Relay that is energized when

In-Rly 1 Alm

m+

Security Level {1}

an external contact closure or opening at

Ignore

[SYSTEM/IN-RLY/RLY-MAP]

the Input Relay 1 connection changes

 

 

state.

 

 

 

Input Relay 4

 

Security Level {1}

The Output Relay that is energized when

In-Rly 4 Alm

m+

[SYSTEM/IN-RLY/RLY-MAP]

an external contact closure or opening at

Ignore

 

the Input Relay 4 connection changes

 

 

 

 

state.

 

 

Input Relay 1 Alias

An alternate name (alias) can be

In-Rly 1

m+

Security Level {1}

assigned to Input Relay 1 if desired.

Input Relay 1

[SYSTEM/IN-RLY/ALIAS]

 

 

 

 

 

 

Input Relay 4 Alias

An alternate name (alias) can be

 

Security Level {1}

assigned to Input Relay 1 if desired

In-Rly 4

m+

[SYSTEM/IN-RLY/ALIAS]

 

Input Relay 4

 

 

Lamp Test

Setting Lamp Test to “ON” will turn on

Lamp Test

m+

Security Level {1}

the “MAJOR”, “MINOR”, “NORMAL”,

OFF

[SYSTEM/DIAG]

“MAJ”, and “MIN” LEDs on the control

 

 

 

unit front panel.

 

 

LVD 1 or 2 Option

Must be set to “Enable” if the unit has an

LVD Option

m+

Security Level {1}

LVD. If the unit has an LVD, but it is

Enable

[MODULES/LVD/SET-ALM]

disabled, the controller will not

 

 

 

disconnect the LVD.

 

 

LVD 1 or 2 Reset

LVD Reset (reconnect) threshold voltage.

LVD Reset

m+

Security Level {1}

 

-48.00 V

[MODULES/LVD/PARAM]

 

 

 

LVD 1 or 2 Trip

LVD Trip (disconnect) threshold voltage.

LVD Trip

m+

Security Level {1}

 

-42.00 V

[MODULES/LVD/PARAM]

 

 

 

LVD Alarm

The output relay that is energized when

LVD Open Alm m+

Security Level {1}

the controller opens the LVD. If unit has

Minor

[MODULES/LVD/SET-ALM]

a battery LVD, no power will be available

 

 

 

to turn on any Output Relays.

 

 

Model Programming

Model type number for the MX28B DC

Model

m+

Security Level {2}

power plant

MX28B-200/400

[SYSTEM/SETUP]

NOTE: Changing the model number

 

 

 

causes the system to reinitialize.

 

 

OEM R Gain

Voltage gain adjustment for factory

OEM R Gain

m+

Security Level {2}

calibration of system voltage

1.000 V

[OEM]

readings/settings.

 

 

OEM R Offset

Voltage offset adjustment for factory

OEM R Offset

m+

Security Level {2}

calibration of system voltage

0.000 V

[OEM]

readings/settings.

 

 

OEM S Gain

Current gain adjustment for factory

OEM S Gain

m+

Security Level {2}

calibration of battery current

1.000 A

[OEM]

readings/settings.

 

 

Page 32

MX28B200/400 –48 VDC User’s Manual (990-9133)

Page 38
Image 38