Ventilation

The rectifier modules for this system have fans that provide front-to-rear airflow for internal cooling. The MX28B housing should mounted such that there is free airflow to the front, top, and bottom of the unit. [Refer to Section 6.6 for environmental characteristics.]

Free airflow should be ensured so that the power system can provide full power at a given ambient temperature rating without de-rating.

3.3. AC Power Connections

WARNING: Ensure that all of the external DC and AC circuit breakers are in the OFF position prior to connecting service to the power plant. Confirm that all voltages have been removed including any battery sources before proceeding.

The MX28B DC power plant requires the supply of 208/220/240/277 VAC single-phase, 50/60 Hz power through individual external 20-amp circuit breakers to the AC input terminal block connections for each rectifier module in the system. Two rectifier modules are required to accommodate the full AC input voltage range. The 1MRF28H54BV rectifier is designed for the standard 208/220/240 VAC input service, while the 1MRF28H54BV50 is used for the 277 VAC input. The AC wiring, from the AC input terminal block connections to the hot-pluggable AC input connector for each rectifier, is factory installed.

The AC input enclosure, located at the top right rear of the MX28B housing, is provided with two one-inch conduit entry holes and an access cover. Inside, a terminal strip(s) for AC input power connection and a separate “Earth Ground” bar for connection of the safety ground wire(s) are provided. The terminal block(s) is labeled as Position 1 through Position 4 (Position 1 through Position 8 for the 400-amp unit) with each position having inputs designated “L1” and “L2/N” for connection of the two AC wires. Positions 1-4 correspond to the top rectifier shelf positions from left to right. Positions 5-8 are applicable to the 400-amp unit only and correspond to the lower rectifier shelf positions from left to right.

The suggested wire size is #10 AWG rated at 90°C or higher; however, the ambient temperature and number of wires in a conduit must also be considered in accordance with NEC requirements. It is suggested that feeds for four rectifiers (8 wires) and one safety ground wire be run in a one-inch conduit; however, be sure to follow any local electrical wiring codes.

If the AC input power is provided from a three-phase distribution panel, the circuit breaker positions should be selected such that the load is balanced as much as possible.