Lincoln 1100 Series Flame will not stay on, Flame Sensor, Power Supply Ignition Control

Models: 1100 Series

1 92
Download 92 pages 44.78 Kb
Page 29
Image 29

Flame will not stay on

Flame Sensor

Power Supply

Ignition Control

Pilot lamp is on, but

Temperature Control

no main flame

 

Thermocouple Probe

Temperature Control

Potentiometer

Impinger II - 1100 Series Service Manual - International

To check for flame sensor operation, connect a digital multimeter (capable of measuring D.C. micro amps) between the flame sensor wire and terminal “F” on the Honeywell Ignition Control or terminal 1 on Landis & Gyr Ignition Control. Sensor current from Honeywell is 2 to 4 D.C. micro amps. Sensor current from Landis & Gyr is 3 micro amps minimum.

If these readings are not achieved replace ignitor/sensor assembly. Also check for any type of damage to flame sensor wire and connections. NOTE: The D.C. micro amp test must be conducted with the oven in low flame (bypass) operation.

Turn the temperature control to the lowest setting. If there is sufficient micro-amp current, but the flame will not stay lit, check

for proper polarity of the power supply If there is sufficient flame sensor current, but the burner will not remain ignited, check the reset button on ignition control. If all above are okay, replace ignition control.

Check for 120 VAC across terminals 10 and 11 on temperature control board. If no voltage is present, check wiring back to the Main Fan Switch. Turn the temperature adjustment knob to the maximum temperature position and check for 120 VAC at the load terminal (number 9), and neutral (number 10).

If 120 VAC is present and unit is not heating, refer to “Solenoid Valve” for next check. If 120 VAC is not present, proceed with next step.

With power on and thermocouple leads attached to board, measure the millivolt output of these leads. Refer to the thermocouple chart in Section D for proper readings.

WITH POWER OFF: Remove the potentiometer leads from the temperature control board and measure ohms from black to whiteleads. The reading should be from approximately 0 to 2.5K ohms as the dial of the potentiometer is turned through its full rotation. From black to red leads, the reading should be approx.2.5K ohms and remain steady throughout the full rotation of the potentiometer.

If the thermocouple probe and the control potentiometer check good,

29

Page 29
Image 29
Lincoln 1100 Series Flame will not stay on, Flame Sensor, Power Supply Ignition Control, Pilot lamp is on, but