Lincoln 1100 Series service manual DC Gearmotor

Models: 1100 Series

1 92
Download 92 pages 44.78 Kb
Page 32
Image 32

DC Gearmotor

Time/Temp Display

12.6 VAC Power

inoperative

Supply

S/N 2011821 & Above

Refer to Page 45

Temp Display out or

NOTE: Time/Temp displays

erratic

uses two types of temperature

 

sensor, Thermistor Probe -

 

2 yellow wires, Thermo-

 

couple Probe - 1 red wire

 

and 1 white wire

 

Thermistor Probe

Thermocouple Probe

changing a board or tach. This test is not always 100% accurate as this test is not performed at operating speeds. However, this test is the best method currently available. Readjustment should always be attempted at least once before replace- ment. See procedure for board adjustment in Section D.

If the problem seems to be the motor or gearbox. Check the brushes in the motor for excessive arcing and/or unusual wear. Check the motor and gearbox from instructions located under “possible cause” listing “Conveyor gear motor”. Measure the transformer primary

for a nominal 120 VAC input.

If 120 VAC primary voltage is not available, refer to the schematic and trace the circuit for incomi ng power failure

Measure the secondary voltage output which will be 12.5 to 15 VAC normally. Recheck secondary output at rear of Time/Temp Display. Terminals 1 to 3 should read 12.5 to 15 VAC. Terminals 1 to 2 and 2 to 3 should be

1/2 of the reading across 1 to 3. If you do not get the above secondary readings, replace the transformer. The older units have a 4 amp ambient fuse in each red secondary lead. These may be jumpered to determine if they are burnt out or intermittent.

Insert the thermocouple of your pyrometer into a finger hole in the top center of the oven. The thermocouple tip should measure air temperature and must not be touching metal. Disconnect the yellow tipped thermistor leads from the time/temp. terminals 9 &10 Measure the resistance of the thermistor probe See the chart in Section D for proper

resistance readings. Inspect the thermistor bulb for itsproper location in its spring holder.Check for short in leads where they enter the sensor bulb. Also check each thermistor lead for short toground. Connect temperature meter to thermocouple at terminals 9 and 10 on back of the time/temp display. (Be sure tomaintain proper polarity on therocouple connections.) Compare actual oventemperature with the reading at the time/temp display. If the temperature readings match, re-calibrate or replace time/temp

32

Impinger II - 1100 Series Service Manual - International

Page 32
Image 32
Lincoln 1100 Series service manual DC Gearmotor