then the problem is usually with thetemperature

 

 

control board.

 

Temperature Control

If 120 VAC is present on the

 

Valve

temperature control board at load

 

 

terminal to neutral, check for voltageat Tempera

 

 

ture Control valve. If voltage is present, listen for

 

 

valve to open and close. Also check for

 

 

opens or shorts in the coil.

 

 

Replace if required.

Intermittent heating

Thermal Overload Of

Both the main fan motor and the

 

Main Fan and Burner

burner blower motor are equipped

 

Blower Motors

with internal thermal protection and

 

 

will cease to operate if overheatingoccurs. As the

 

 

motors overheat and then cool, this will cause the

 

 

unitsto cycle on and off intermittently.

 

 

This may be caused by improper ventilation or

 

 

preventativemaintenance. Also, most of the

 

 

problems listed under “Oven Will Not

 

 

Heat” can cause intermittent failure.

Conveyor will not run

3 Amp Fuse

Check and replace if defective.

 

Fuseholder

Check and replace if defective.

 

Fan Switch

Check for continuity between switch

 

 

terminals.

S/N 2011821 & Above

Conveyor Switch

Check for continuity between switch

Refer to Page 45

 

terminals.

 

Speed Adjustment

This is a 0 to 5 K ohm, 10 turn

 

Potentiometer.

WITH POWER OFF: Remove the red, black

 

 

and white pot. leads from the motor control

 

 

board at terminalsP1, P2 and P3. With a

 

 

digital multimeter, check the ohm reading

 

 

across the red lead to the black lead. This

 

 

reading shouldbe 5 K ohms ± 5% as the pot is

 

 

rotated from low to high.Place the meter leads on

 

 

the redlead and on the white lead.Rotating the

 

 

pot. slowly, from low to high, the meter reading

 

 

should show an even transition from 0 to

 

 

5 K ohms ± 5%. There should be

 

 

no dead or open spots through out

 

 

the 10 turns of the pot.

 

 

Check all three leads to ground.

 

 

There should be no continuity to

 

 

ground. If any of the above checks

 

 

fail, replace the pot.

 

DC Motor Control Board

Check for 120 VAC input to the

 

 

control board at terminals L1 and

 

 

L2. If not present, check the

 

 

conveyor switch and wiring back to the

 

 

3 amp fuse and then back to the power

 

 

source if necessary. If 120 VAC is

 

 

present at L1 and L2, check the VDC

 

 

output at terminals A+ and A-. If a

 

 

DC voltage is not present, check the

 

 

4 amp and the 1 amp fuses on the

30

Impinger II - 1100 Series Service Manual - International

Page 30
Image 30
Lincoln 1100 Series service manual then the problem is usually with thetemperature