|
| then the problem is usually with thetemperature |
|
| control board. |
| Temperature Control | If 120 VAC is present on the |
| Valve | temperature control board at load |
|
| terminal to neutral, check for voltageat Tempera |
|
| ture Control valve. If voltage is present, listen for |
|
| valve to open and close. Also check for |
|
| opens or shorts in the coil. |
|
| Replace if required. |
Intermittent heating | Thermal Overload Of | Both the main fan motor and the |
| Main Fan and Burner | burner blower motor are equipped |
| Blower Motors | with internal thermal protection and |
|
| will cease to operate if overheatingoccurs. As the |
|
| motors overheat and then cool, this will cause the |
|
| unitsto cycle on and off intermittently. |
|
| This may be caused by improper ventilation or |
|
| preventativemaintenance. Also, most of the |
|
| problems listed under “Oven Will Not |
|
| Heat” can cause intermittent failure. |
Conveyor will not run | 3 Amp Fuse | Check and replace if defective. |
| Fuseholder | Check and replace if defective. |
| Fan Switch | Check for continuity between switch |
|
| terminals. |
S/N 2011821 & Above | Conveyor Switch | Check for continuity between switch |
Refer to Page 45 |
| terminals. |
| Speed Adjustment | This is a 0 to 5 K ohm, 10 turn |
| Potentiometer. | WITH POWER OFF: Remove the red, black |
|
| and white pot. leads from the motor control |
|
| board at terminalsP1, P2 and P3. With a |
|
| digital multimeter, check the ohm reading |
|
| across the red lead to the black lead. This |
|
| reading shouldbe 5 K ohms ± 5% as the pot is |
|
| rotated from low to high.Place the meter leads on |
|
| the redlead and on the white lead.Rotating the |
|
| pot. slowly, from low to high, the meter reading |
|
| should show an even transition from 0 to |
|
| 5 K ohms ± 5%. There should be |
|
| no dead or open spots through out |
|
| the 10 turns of the pot. |
|
| Check all three leads to ground. |
|
| There should be no continuity to |
|
| ground. If any of the above checks |
|
| fail, replace the pot. |
| DC Motor Control Board | Check for 120 VAC input to the |
|
| control board at terminals L1 and |
|
| L2. If not present, check the |
|
| conveyor switch and wiring back to the |
|
| 3 amp fuse and then back to the power |
|
| source if necessary. If 120 VAC is |
|
| present at L1 and L2, check the VDC |
|
| output at terminals A+ and |
|
| DC voltage is not present, check the |
|
| 4 amp and the 1 amp fuses on the |
30 | Impinger II - 1100 Series Service Manual - International |