American Power Conversion RT XLI/XLICH user manual

Models: RT XLI/XLICH

1 34
Download 34 pages 44.93 Kb
Page 28
Image 28

Condition

PowerView Display

Reason for Message

Corrective Action

Message

 

 

 

 

 

 

 

General

# of batteries increased.

At least one battery pair has been

No corrective action is necessary.

Status

 

added to the system.

 

 

 

 

 

 

# of batteries decreased.

At least one battery pair has been

 

 

 

removed from the system.

 

 

 

 

 

 

# External Battery Packs

At least one external battery pack has

 

 

increased.

been connected to the UPS.

 

 

 

 

 

 

# External Battery Packs

At least one external battery pack has

 

 

decreased.

been disconnected from the UPS.

 

 

 

 

 

Module

Bad Battery Pair.

A battery pair has failed and requires

Refer to battery pair installation in

Failure

 

replacement.

the external battery pack user

 

 

 

manual.

 

 

 

 

Threshold

Load Power Is Above

The load has exceeded the user-

Option 1) Use the display interface to

Alarm

Alarm Limit.

specified load alarm threshold.

raise the alarm threshold.

 

 

 

Option 2) Reduce the load

 

 

 

 

 

Load Is No Longer Above

The load exceeded the alarm

No corrective action is necessary.

 

Alarm Threshold.

threshold. The situation has been

 

 

 

corrected. Either because the load

 

 

 

decreased or the threshold was

 

 

 

increased.

 

 

 

 

 

 

Min Runtime Restored.

The system runtime dropped below

 

 

 

the configured minimum and has been

 

 

 

restored:

 

 

 

1) Additional battery modules were

 

 

 

installed.

 

 

 

2) The existing battery modules were

 

 

 

recharged.

 

 

 

3) The load was reduced.

 

 

 

4) The user- specified threshold was

 

 

 

decreased.

 

 

 

 

 

24

Smart-UPS RT 15000/20000 VA 230 Vac Stack/Rack-Mount 6U User Manual

Page 28
Image 28
American Power Conversion RT XLI/XLICH user manual