Specifications

Environmental Specifications

Temperature

32° to 104° F (0° to 40° C)

This unit is intended for indoor use only.

Operating

Select a location sturdy enough to handle

Storage

5° to 113° F (-15°to 45° C) charge the UPS battery every

the weight.

 

six months

Do not operate the UPS where there is

 

86° to 158° F (30° to 70° C) charge the UPS battery every

 

excessive dust or the temperature or

 

three months

 

humidity are outside the specified limits.

 

 

Maximum

 

This unit has front to rear airflow. Allow

Elevation

 

adequate space for proper ventilation.

Operating

10,000 ft (3,000 m)

Environmental factors impact battery life.

Storage

50,000 ft (15,240 m)

High temperatures, poor utility power, and

 

 

Humidity

0 to 95% relative humidity, non-condensing

frequent, short duration discharges will

shorten battery life.

 

 

 

 

 

 

 

 

Physical Specifications

 

 

 

 

 

 

 

 

 

 

Weight (unpacked)

 

 

 

 

 

 

 

 

 

 

 

UPS

145 lbs (66 kg)

 

 

 

 

 

 

 

 

 

 

XL Battery Pack

 

 

 

 

 

with eight battery

400 lbs (181 kg)

 

 

 

 

modules

 

 

 

 

 

 

 

 

 

 

 

Each battery

38 lbs (17 kg)

 

 

 

 

module

 

 

 

 

 

 

 

 

 

 

Maximum Number of XLBPs Supported by the Smart-UPS XL

10

Dimensions

 

 

 

 

 

482 mm

 

 

 

19 in

 

 

 

465 mm

 

 

 

18.3 in

 

 

 

432 mm

773 mm

 

 

17 in

30.4 in

263 mm 10.4 in

102 mm

4 in

 

2

Smart-UPS RT 15000/20000 VA 230 Vac Stack/Rack-Mount 6U User Manual

Page 6
Image 6
American Power Conversion RT XLI/XLICH user manual Environmental Specifications, Physical Specifications