American Power Conversion RT XLI/XLICH user manual Wiring Specifications

Models: RT XLI/XLICH

1 34
Download 34 pages 44.93 Kb
Page 14
Image 14

Wiring Specifications

Adhere to national and local electrical codes when wiring.

 

Input Connections

 

 

Output Connections

 

Main Input

 

 

 

Hardwire

 

 

Single-Phase: Wire to L1, N, and

 

 

Single-Phase: Wire to L1, N, and

 

Three-Phase: Wire to L1, L2, L3, N, and

 

Three-Phase: Wire to L1, L2, L3, N, and

 

Bypass Input (optional)

 

 

Single-phase PDU

 

 

Single-Phase: Wire to B1, N, and

 

 

XL battery pack PDU to UPS: Wire L1, N,

 

 

 

 

 

 

Three-Phase: Wire to B1, B2, B3, N, and

 

 

 

 

System

Wiring

Number

Voltage

Current

External Input

Wire Size

 

 

of Phases

 

Full Load

Circuit Breaker

(typical)*

 

 

 

 

(maximum

(typical)

 

SURT15000XLI/

Input

1

220/230/

83 A

100 A / 1-pole

25/35 mm2

XLICH

 

 

240 Vac

 

 

(2/1 AWG)

 

Input

3

380/400/

28 A / phase

35 A / 3-pole

6 mm2

 

 

 

415 Vac

 

 

(8 AWG)

 

Output

1

220/230/

65 A

not required

25 mm2

 

 

 

240 Vac

 

 

(2 AWG)

 

Output

3

380/400/

22 A / phase

not required

6 mm2

 

 

 

415 Vac

 

 

(8 AWG)

SURT20000XLI/

Input

1

220/230/

105 A

125 A / 1-pole

35/50 mm2

XLICH

 

 

240 Vac

 

 

(1/0 AWG)

 

Input

3

380/400/

35 A / phase

50 A / 3-pole

10 mm2

 

 

 

415 Vac

 

 

(6 AWG)

 

Output

1

220/230/

87 A

not required

35 mm2

 

 

 

240 Vac

 

 

(1 AWG)

 

Output

3

380/400/

29 A / phase

not required

10 mm2

 

 

 

415 Vac

 

 

(6 AWG)

*Terminal screw tightening torque: 40 lbf-in (4.5 N-m) The acceptable input frequency range is 40 to 70 Hz.

The output frequency is user selectable. Refer to the PowerView display menu screens for available options.

10

Smart-UPS RT 15000/20000 VA 230 Vac Stack/Rack-Mount 6U User Manual

Page 14
Image 14
American Power Conversion RT XLI/XLICH Wiring Specifications, Adhere to national and local electrical codes when wiring