Condition | PowerView Display | Reason for Message | Corrective Action | |
Message | ||||
|
|
| ||
|
|
|
| |
General | Need Bat Replacement. | One or more battery pairs are in need | Refer to battery installation | |
Fault |
| of replacement. | procedure. | |
|
|
|
| |
| No Batteries Are | No battery power is available. | Check that batteries are installed and | |
| Connected. |
| connected properly. | |
|
|
|
| |
| Discharged Battery. | The UPS is on battery operation and | Shut down the system and the load | |
|
| the battery charge is low. | or restore the incoming voltage. | |
|
|
|
| |
| Low- Battery. | The UPS is on battery operation and |
| |
|
| the battery charge is low. |
| |
|
|
|
| |
| Weak Batt(s) Detected. | One or more weak battery pairs | Replace the weak battery pairs. | |
| Reduced Runtime. | detected (only applicable for internal |
| |
|
| battery modules). |
| |
|
|
|
| |
| Batt Temperature Exceeded | The temperature of one or more | Contact APC Customer Support. | |
| Upper Limit. | battery packs has exceeded system | Refer to Contact Information in this | |
|
| specifications. | manual. | |
|
|
|
| |
| Battery | The battery voltage is too high and the |
| |
| Warning. | charger has been deactivated. |
| |
|
|
|
| |
| Runtime Is Below Alarm | The predicted runtime is lower than | Option 1) Allow the batteries to | |
| Threshold. | the | recharge. | |
|
| alarm threshold. Either the battery | Option 2) If possible, increase the | |
|
| capacity has decreased, or the load has | number of battery modules. | |
|
| increased. | Option 3) Reduce the load. | |
|
|
| ||
|
|
| Option 4) Decrease the alarm | |
|
|
| threshold. | |
|
|
|
|
25 |