Condition

PowerView Display

Reason for Message

Corrective Action

Message

 

 

 

 

 

 

 

General

Need Bat Replacement.

One or more battery pairs are in need

Refer to battery installation

Fault

 

of replacement.

procedure.

 

 

 

 

 

No Batteries Are

No battery power is available.

Check that batteries are installed and

 

Connected.

 

connected properly.

 

 

 

 

 

Discharged Battery.

The UPS is on battery operation and

Shut down the system and the load

 

 

the battery charge is low.

or restore the incoming voltage.

 

 

 

 

 

Low- Battery.

The UPS is on battery operation and

 

 

 

the battery charge is low.

 

 

 

 

 

 

Weak Batt(s) Detected.

One or more weak battery pairs

Replace the weak battery pairs.

 

Reduced Runtime.

detected (only applicable for internal

 

 

 

battery modules).

 

 

 

 

 

 

Batt Temperature Exceeded

The temperature of one or more

Contact APC Customer Support.

 

Upper Limit.

battery packs has exceeded system

Refer to Contact Information in this

 

 

specifications.

manual.

 

 

 

 

 

Battery Over-Voltage

The battery voltage is too high and the

 

 

Warning.

charger has been deactivated.

 

 

 

 

 

 

Runtime Is Below Alarm

The predicted runtime is lower than

Option 1) Allow the batteries to

 

Threshold.

the user-specified minimum runtime

recharge.

 

 

alarm threshold. Either the battery

Option 2) If possible, increase the

 

 

capacity has decreased, or the load has

number of battery modules.

 

 

increased.

Option 3) Reduce the load.

 

 

 

 

 

 

Option 4) Decrease the alarm

 

 

 

threshold.

 

 

 

 