External Connections

Notes:

As a standard, the Smart-UPS DP is made for single-phase connection.

Due to the leakage current of 3.5 to 10 mA, the Smart-UPS DP must always be grounded according to local regulations.

Mains Connections

Make these connections only if no optional equipment (see the Optional Equipment Installation, page 8) is being used.

Mains Fuses and Cable Dimensions

Standard System

System

Mains Fuse * (Fm)

Input Cable UPS

Output Cable UPS

4kV

25A

3x6 mm²

3x4 mm²

6kV

40A

3x10 mm²

3x10 mm²

8kV

50A

3x16 mm²

3x10 mm²

10kV

63A

3x16 mm²

3x16 mm²

* Din gl Types

MAINS

Fm

L

N

PE

INPUT CABLE UPS

OUTPUT CABLE UPS

LOAD L

N

L

N

L

N

+

UPS

COM

EPO

PORT

 

990-1007A, Revision 2 9/99