Wiring Specifications

Adhere to national and local electrical codes when wiring.

 

Input Connections

 

 

Output Connections

 

Main Input

 

 

Hardwire

 

 

Single-Phase: Wire to L1, N, and

 

Single-Phase: Wire to L1, N, and

 

Three-Phase: Wire to L1, L2, L3, N, and

Three-Phase: Wire to L1, L2, L3, N, and

 

Bypass Input (optional)

 

Single-phase PDU

 

 

Single-Phase: Wire to B1, N, and

 

XL battery pack PDU to UPS: Wire L1, N,

 

 

 

 

 

Three-Phase: Wire to B1, B2, B3, N, and

 

 

 

 

System

Wiring

Number

Voltage

Current

External Input

Wire Size

 

 

of Phases

 

Full Load

Circuit Breaker

(typical)*

 

 

 

 

(maximum)

(typical)

 

SURT15000UXI/

Input

1

220/230/

83 A

100 A / 1-pole

25/35 mm2

UXICH

 

 

240 Vac

 

 

(2/1 AWG)

 

Input

3

380/400/

28 A / phase

35 A / 3-pole

6 mm2

 

 

 

415 Vac

 

 

(8 AWG)

 

Output

1

220/230/

65 A

not required

25 mm2

 

 

 

240 Vac

 

 

(2 AWG)

 

Output

3

380/400/

22 A / phase

not required

6 mm2

 

 

 

415 Vac

 

 

(8 AWG)

SURT20000XI/

Input

1

220/230/

105 A

125 A / 1-pole

35/50 mm2

UXICH

 

 

240 Vac

 

 

(1/0 AWG)

 

Input

3

380/400/

35 A / phase

50 A / 3-pole

10 mm2

 

 

 

415 Vac

 

 

(6 AWG)

 

Output

1

220/230/

87 A

not required

35 mm2

 

 

 

240 Vac

 

 

(1 AWG)

 

Output

3

380/400/

29 A / phase

not required

10 mm2

 

 

 

415 Vac

 

 

(6 AWG)

*Terminal screw tightening torque: 40 lbf-in (4.5 N-m) The acceptable input frequency range is 40 to 70 Hz.

The output frequency is user selectable. Refer to the PowerView display menu screens for available options.

8

Smart-UPS RT 15000/20000 VA 230 Vac UXI/UXICH Tower User Manual

Page 12