CLEARANCES (EXTERIOR)

INSTALLATION CONSIDERATIONS

Table 2

MINIMUM CLEARANCES TO COMBUSTIBLE SURFACES

“A” - Right Side

“B” - Left Side

“C” - Back

5” (12.7 cm)

5” (12.7 cm)

5” (12.7 cm)

A, B, and C clearances to non-combustible surfaces is “0” inches. A 20” clearance to cover remains unchanged.

CLEARANCES (EXTERIOR)

The illustration below shows the required clearances for venting units using natural draft venting. The vent must extend at least 3 feet above the highest point where it passes through a roof of a building and at least 2 feet higher than any portion of a building within a horizontal distance of 10 feet (for vents of 12 inches in diameter or less).

Reference: NFPA 54 ANSI Z 223.1.

Figure 6