American Water Heater (A)BCG385T500-8N, (A)BCG38T500-8P manual Blower Prover Switch - Settings

Models: (A)BCG38T500-8P (A)BCG385T500-8N

1 40
Download 40 pages 7.85 Kb
Page 19
Image 19
BLOWER PROVER SWITCH - SETTINGS

OPERATION AND SERVICE

BLOWER PROVER SWITCH - SETTINGS

 

 

 

Vent Connection

Blower Prover Switch

Exhaust/Outlet

 

 

 

 

Optional Hot Water Outlet

Blower (Draft Inducer)

Figure 15

Table 4

BLOWER PROVER SWITCH TABLE

Model

Pressure Setting to Close Switch (Inches W.C.)

(A)BCG385T500-8N/8P

-2.85” ± 0.13”

NOTE: The Blower Prover Switch contacts are normally open and will close on a fall in pressure. This will be a negative pressure (i.e., a vacuum).

Servicing should only be performed by a Qualified Service Agent

19

Page 19
Image 19
American Water Heater (A)BCG385T500-8N, (A)BCG38T500-8P manual Blower Prover Switch - Settings