American Water Heater (A)BCG385T500-8N, (A)BCG38T500-8P manual Manifold Pressure Adjustment

Models: (A)BCG38T500-8P (A)BCG385T500-8N

1 40
Download 40 pages 7.85 Kb
Page 17
Image 17
Manifold Pressure Adjustment

OPERATION AND SERVICE

Manifold Pressure Adjustment

The main gas regulators are found beneath the silver or black cap screws. (Natural Gas valves have silver caps; Propane valves have a black caps). Remove the caps to access the outlet (manifold) pressure adjustment screw. IMPORTANT: Ensure that the outlet pressure matches the manifold pressure that is listed on the water heater rating plate.

Natural Gas valves are factory preset to 3.5 inches W.C. The full rate outlet pressure range is between 3 and 5 inches W.C.

Propane (LP) valves are factory preset to 10.0 inches W.C. The full rate outlet pressure range is between 8 and 12 inches W.C.

Caution: Always test the manifold pressure at the outlet when the gas is flowing.

Wiring Harness

Main Gas

 

Regulators

(Outlet Pressure

Adjustment)

Lead Wires

(24-Volt Main Valve

Solenoid Connections)

TOP VIEW OF GAS VALVE

Figure 13

Main Valve Solenoid Connections

The figure above shows the two 24-volt main valve (MV) solenoid connections. The two yellow wires from the 12-pin ignition board plug connect to these leads.

Servicing should only be performed by a Qualified Service Agent

17

Page 17
Image 17
American Water Heater (A)BCG385T500-8N, (A)BCG38T500-8P manual Manifold Pressure Adjustment, Main Valve Solenoid Connections