Upgrading the Docking Station Firmware

Displays the current

docking station firmware version

FIG. 2 Batteries page

The docking station firmware is shown on the right of the Batteries page.

Verify you have downloaded the latest firmware file from www.amx.com and then save the Kit file to your computer.

Step 2: Upgrade the Docking Station firmware via USB

1.Configure the panel for a USB Connection Type.

2.Prepare NetLinx Studio for communication to the panel via a Virtual Master.

Refer to the MVP-7500/8400 Operation/Reference Guide (available online at

www.amx.com) for information on configuring communications on the panel.

3.After the Communication Verification dialog window verifies active communication between the Virtual Master and the panel, click the OnLine Tree tab in the Workspace window to view the devices on the Virtual System. The default System value is one.

4.Right-click on the System entry and select Refresh System to re-populate the list. Verify the panel appears in the OnLine Tree tab of the Workspace window. The default Modero panel value is 10001.

5.Locate the latest firmware file from the www.amx.com > Tech Center > Downloadable Files > Firmware Files > Modero Panels firmware (MVP Docking Stations: MVP-TDS/WDS)section of the website.

6.Click on the desired Kit file link and after you’ve accepted the Licensing Agreement, verify you have downloaded the Docking Station Kit file to a known location.

7.Select Tools > Firmware Transfers > Send to NetLinx Device from the Main menu to open the Send to NetLinx Device dialog (FIG. 3). Verify the panel’s System and Device number values match those values listed within the System folder in the OnLine Tree tab of the Workspace window.

8.Select the docking station’s Kit file (ending in VXX.kit) from the Files section (FIG. 3).

9.Enter the Device number associated with the panel and the System number associated with the Master (listed in the OnLine Tree tab of the Workspace window). The Port field is greyed-out.

10

MVP-TDS Table Docking Station for MVP Panels

Page 16