AMX NXA-UPS1500 Product Specifications, NXA-UPS1500 Uninterruptible Power Supply, Input

Models: NXA-UPS1500

1 40
Download 40 pages 20.79 Kb
Page 6
Image 6
Product Specifications

NXA-UPS1500 Uninterruptible Power Supply

Product Specifications

NXA-UPS1500 Product Specifications

Input:

Voltage Window (DIP Switch selectable):

 

120V version (FG678-15): 110/115/120 Vac +35% ˜ -32%

 

240V version (FG678-20): 220/230/240 Vac +35% ˜ -32%

 

Frequency: 45 ˜ 65Hz (50/60Hz auto-sensing)

 

 

Output:

Voltage Window (AC Mode):

 

120V version (FG678-15): 110/115/120 Vac +8% ˜ -12%

 

240V version (FG678-20): 220/230/240 Vac +8% ˜ -12%

 

Voltage Window (INV Mode):

 

120V version (FG678-15): 110/115/120 Vac +/-5%

 

240V version (FG678-20): 220/230/240 Vac +/-5%

 

• Capacity (VA/W):1500/900

 

• Wave Form: Pure sine wave

 

• Frequency: 50Hz/60Hz +/-0.1Hz

 

• Transfer Time:2 ms typical

 

• Autonomy: > 8 min.

 

• DC Start: Yes

 

 

Battery:

• Type: 12V, sealed lead acid maintenance-free

 

• Capacity: 9AH

 

• Quantity: 4 12V batteries required

 

• Voltage:

 

120V version (FG678-15): 24 Vdc

 

240V version (FG678-20): 48 Vdc

 

• Recharge Time: 2 ˜ 4 hours to 90%

 

• Storage: Store at -15 to +30 °C (+5 to +86 °F), charge the UPS battery every 6

 

months / Store at +30 to +45 °C (+86 to +113 °F), charge the UPS battery every

 

3 months.

 

 

LED indicators:

• Utility mode

 

• Backup mode

 

• Battery conditions

 

 

Display LCD:

• Load level (%)

 

• Battery level (%)

 

• Bypass

 

AVR-Boost/AVR Buck

 

• Battery Low/Replace/Fault

 

• UPS Fault

 

• Site Wiring Fault

 

• Overload

 

 

Overload Protection:

• AC Mode: >110% Buzzer continuously alarms, and shuts down in 10 minutes.

 

• Inverter Mode: >120% Buzzer continuously alarms, and shuts down in 10

 

seconds.

 

 

Short Circuit Protection:

• AC Mode: Breaker and electronic circuit

 

• Inverter Mode: Shut down automatically in 8 cycles

 

 

Self-Diagnostics:

• Upon Power-on

 

 

Alarms:

• Line Failure

 

• Battery Low

 

• Overload and Fault

 

 

Operation Environment:

• Temperature: 32° - 104°F (0-40° C)

 

• Operation Humidity: 95% RH Maximum, non-condensing

 

 

 

 

 