Communication and Firmware Update
the Master to reboot. The STATUS and OUTPUT LEDs should begin to alternately blink during the incorporation. Wait until the STATUS LED is the only LED to blink.
7.
8.Use Ctrl+S to save your existing NetLinx Project with the new changes.
If the NetLinx device does not appear within the OnLine Tree tab of the Workspace window of NetLinx Studio, make sure that the NetLinx Master System Number (from within the Device Addressing tab) is correctly assigned. If there is a problem, use a
system value of zero (0) on the NetLinx device.
The Master is default set to DEVICE 0. Connected NetLinx device addresses can only be changed through the Protected Setup page. The new address is reflected within the OnLine Tree tab of the Workspace window only after the devices are rebooted and the system is refreshed.
Working with multiple NetLinx Masters
When using more than one Master, each unit must be assigned to a separate System value.
A Master’s System value can be changed but its’ device Address must always be set to zero (00000). The Device Addressing dialog will not allow you to alter the NetLinx Master address value.
Example: Using NetLinx Studio 2.1 to work with an
The
The
Changing the system value on the Modero panel
The system value on a Modero touch panel can not be changed from the Device
Addressing dialog.
1.Press and hold the grey Front Setup Access button (below the LCD) for 3 seconds to access the Setup page.
2.Press the Protected Setup button to access the Protected Setup page.
3.Use the
4.Press the System Connection button.
5.Press the blue System field on the right of the page to open the Master System Number keypad.
6.Enter the new System value (associated with the Master connected to the panel).
7.Press Back to save your changes and return to the Protected Setup page.
8.Press the
9.
10.Use Ctrl+S to save your existing NetLinx Project with the new changes.