Step 1

Note: Thoroughly clean exposed portions of grounding cables, unplated portion of uni- versal terminals and cor-responding mounting surfaces using a wire brush. Liberally apply supplied 203233-2 conductive grease to all connection surfaces prior to and after instal- lation. Thoroughly remove conductive grease from hands and tools using soap and water.

Refer to Figure 68. Attach lugs to universal terminals at each end of 46373 grounding cables as shown, using 5/16 by 1 inch (25 mm) bolts, flat washers and nuts. Install grounding cables on 7/8 by 2-3/4 inch (70 mm) bolts at indicated positions.