UPS theory of operation

Unitary UPS

The unitary MGETM GalaxyTM 6000

rectifier-charger;

The load and Mains 2 operate at 50

UPSs are made up of five modular

battery;

or 60 Hz.

sub-assemblies:

three-phase inverter;

 

 

static switch;

 

 

maintenance bypass.

 

 

 

 

 

Mains 1 power up

the inverter receives power from the rectifier-charger and supplies power to the load. There is no direct connection between Mains and load;

the battery is charged or the charge maintained.

static by-pass switch

Mains 2

rectifier-

chargerinverter

Mains 1

battery

load

Mains 1 power down

the inverter receives power from the battery and supplies power to the load;

the battery discharges.

Major overload

Mains 2

rectifier- charger

Mains 1

static by-pass switch

inverter

battery

load

Mains 2 supplies power to the load via the static switch;

the inverter is shut down;

the inverter starts-up automatically as soon as overload is removed;

power is transferred without affecting the load.

Maintenance

static by-pass switch

Mains 2

rectifier-

chargerinverter

Mains 1

load

battery

Mains 2 supplies power to the load via the maintenance bypass;

the rectifier-charger and inverter are shut down and disconnected from all sources of power.

Mains 2

rectifier- charger

Q1

Mains 1

Q3BP

static by-pass switch

Q4S

inverter

Q5N

load

QF1

battery

Page 18 - 6739389EN/FB