System information (continued)

Battery and adjustments fields

Legend:

no entry: not available;

yes: available in this cubicle;

bat: available in this cubicle if battery installed;

bat/opt: available if option installed.

Inverter type:

0: unitary;

1: parallel without static switch;

2: parallel with static switch;

3: Static Switch cubicle.

Battery installed:

0 = no;

1 = yes.

Sensor installed:

0 = no;

1 = yes.

Tables of binary data

Rectifier-charger

Legend:

no entry: not available;

yes: available in this cubicle;

bat: available in this cubicle if battery installed.

battery measurements

units

JBUS address

type

 

 

 

 

hex. word

unitary

parallel

SS

U battery

V

1C0

yes

yes

 

 

 

 

 

 

 

I battery

A

1C1

bat

bat

 

 

 

 

 

 

 

battery backup time

mn

1C2

bat/opt

bat/opt

 

 

 

 

 

 

 

battery room temperature

°C

1C3

bat/opt

bat/opt

 

 

 

 

 

 

 

battery adjustments

units

JBUS address

type

 

 

 

 

hex. word

unitary

parallel

SS

inverter type

-

200

yes

yes

yes

 

 

 

 

 

 

battery installed

-

201

yes

yes

 

 

 

 

 

 

 

battery temperat. sensor

-

202

yes

yes

 

 

 

 

 

 

 

In (I rated load)

A

208

yes

yes

yes

 

 

 

 

 

 

Pn (P rated load)

kW

209

yes

yes

yes

rectifier-charger

bit meaning

 

JBUS

type

 

 

information

 

 

address

 

 

 

 

 

 

hex.

 

 

 

 

 

bit=0

bit=1

bit

word

unit.

para.

SS

B_Etat_QF1

open

closed

400

40

bat

bat

 

B_Etat_Dech_Bat

not discharging

discharging

401

 

bat

bat

 

 

 

 

 

 

 

 

 

B_Etat_Ubat_Min

not reached

min. volt. fault

402

 

bat

bat

 

 

 

 

 

 

 

 

 

B_Etat_Ubat_Aut

not reached

warning

403

 

bat

bat

 

 

 

 

 

 

 

 

 

B_Etat_Tempe_Ht

normal

outside toleran.

404

 

bat

bat

 

 

 

 

 

 

 

 

 

B_Etat_Res1_Ht

not reached

outside toleran.

405

 

bat

bat

 

 

 

 

 

 

 

 

 

B_Etat_Vent_Bat

no fault

fault

406

 

yes

yes

 

 

 

 

 

 

 

 

 

B_Etat_Cha_Bat

not charging

charging

407

 

bat

bat

 

 

 

 

 

 

 

 

 

B_Etat_Pont

off

on

408

 

bat

bat

 

 

 

 

 

 

 

 

 

B_Etat_Def_Maj_Cha

no fault

fault

409

 

yes

yes

 

 

 

 

 

 

 

 

 

B_Etat_Q1

open

closed

40E

 

yes

yes

 

 

 

 

 

 

 

 

 

B_Etat_Arr_Urg

not activated

activated

411

41

yes

yes

 

 

 

 

 

 

 

 

 

B_Etat_U_Res1

normal

outside toleran.

412

 

yes

yes

 

 

 

 

 

 

 

 

 

B_Etat_F_Res1

normal

outside toleran.

413

 

yes

yes

 

 

 

 

 

 

 

 

 

B_Etat_Arr_Prog

not activated

activated

417

 

bat

bat

 

 

 

 

 

 

 

 

 

B_Etat_Lim_Groupe

not activated

activated

419

 

bat

bat

 

 

 

 

 

 

 

 

 

B_Etat_IBat_Aux

not activated

activated

41A

 

bat

bat

 

 

 

 

 

 

 

 

 

B_Etat_Egal_Bat

not active

active

41B

 

bat

bat

 

 

 

 

 

 

 

 

 

B_Etat_Groupe

not activated

activated

41E

 

yes

yes

 

6739389EN/FB - Page 31