System information (continued)
Battery and adjustments fields
Legend:
◗no entry: not available;
◗yes: available in this cubicle;
◗bat: available in this cubicle if battery installed;
◗bat/opt: available if option installed.
Inverter type:
◗0: unitary;
◗1: parallel without static switch;
◗2: parallel with static switch;
◗3: Static Switch cubicle.
Battery installed:
◗0 = no;
◗1 = yes.
Sensor installed:
◗0 = no;
◗1 = yes.
Tables of binary data
Rectifier-charger 
Legend:
◗no entry: not available;
◗yes: available in this cubicle;
◗bat: available in this cubicle if battery installed.
battery measurements  | units  | JBUS address  | type  | 
  | 
  | 
  | 
  | hex. word  | unitary  | parallel  | SS  | 
U battery  | V  | 1C0  | yes  | yes  | 
  | 
  | 
  | 
  | 
  | 
  | 
  | 
I battery  | A  | 1C1  | bat  | bat  | 
  | 
  | 
  | 
  | 
  | 
  | 
  | 
battery backup time  | mn  | 1C2  | bat/opt  | bat/opt  | 
  | 
  | 
  | 
  | 
  | 
  | 
  | 
battery room temperature  | °C  | 1C3  | bat/opt  | bat/opt  | 
  | 
  | 
  | 
  | 
  | 
  | 
  | 
battery adjustments  | units  | JBUS address  | type  | 
  | 
  | 
  | 
  | hex. word  | unitary  | parallel  | SS  | 
inverter type  | -  | 200  | yes  | yes  | yes  | 
  | 
  | 
  | 
  | 
  | 
  | 
battery installed  | -  | 201  | yes  | yes  | 
  | 
  | 
  | 
  | 
  | 
  | 
  | 
battery temperat. sensor  | -  | 202  | yes  | yes  | 
  | 
  | 
  | 
  | 
  | 
  | 
  | 
In (I rated load)  | A  | 208  | yes  | yes  | yes  | 
  | 
  | 
  | 
  | 
  | 
  | 
Pn (P rated load)  | kW  | 209  | yes  | yes  | yes  | 
bit meaning  | 
  | JBUS | type | 
  | 
  | ||
information | 
  | 
  | address | 
  | 
  | 
  | |
  | 
  | 
  | hex. | 
  | 
  | 
  | 
  | 
  | bit=0 | bit=1 | bit  | word | unit. | para. | SS  | 
B_Etat_QF1  | open  | closed  | 400  | 40  | bat  | bat  | 
  | 
B_Etat_Dech_Bat  | not discharging  | discharging  | 401  | 
  | bat  | bat  | 
  | 
  | 
  | 
  | 
  | 
  | 
  | 
  | 
  | 
B_Etat_Ubat_Min  | not reached  | min. volt. fault  | 402  | 
  | bat  | bat  | 
  | 
  | 
  | 
  | 
  | 
  | 
  | 
  | 
  | 
B_Etat_Ubat_Aut  | not reached  | warning  | 403  | 
  | bat  | bat  | 
  | 
  | 
  | 
  | 
  | 
  | 
  | 
  | 
  | 
B_Etat_Tempe_Ht  | normal  | outside toleran.  | 404  | 
  | bat  | bat  | 
  | 
  | 
  | 
  | 
  | 
  | 
  | 
  | 
  | 
B_Etat_Res1_Ht  | not reached  | outside toleran.  | 405  | 
  | bat  | bat  | 
  | 
  | 
  | 
  | 
  | 
  | 
  | 
  | 
  | 
B_Etat_Vent_Bat  | no fault  | fault  | 406  | 
  | yes  | yes  | 
  | 
  | 
  | 
  | 
  | 
  | 
  | 
  | 
  | 
B_Etat_Cha_Bat  | not charging  | charging  | 407  | 
  | bat  | bat  | 
  | 
  | 
  | 
  | 
  | 
  | 
  | 
  | 
  | 
B_Etat_Pont  | off  | on  | 408  | 
  | bat  | bat  | 
  | 
  | 
  | 
  | 
  | 
  | 
  | 
  | 
  | 
B_Etat_Def_Maj_Cha  | no fault  | fault  | 409  | 
  | yes  | yes  | 
  | 
  | 
  | 
  | 
  | 
  | 
  | 
  | 
  | 
B_Etat_Q1  | open  | closed  | 40E  | 
  | yes  | yes  | 
  | 
  | 
  | 
  | 
  | 
  | 
  | 
  | 
  | 
B_Etat_Arr_Urg  | not activated  | activated  | 411  | 41  | yes  | yes  | 
  | 
  | 
  | 
  | 
  | 
  | 
  | 
  | 
  | 
B_Etat_U_Res1  | normal  | outside toleran.  | 412  | 
  | yes  | yes  | 
  | 
  | 
  | 
  | 
  | 
  | 
  | 
  | 
  | 
B_Etat_F_Res1  | normal  | outside toleran.  | 413  | 
  | yes  | yes  | 
  | 
  | 
  | 
  | 
  | 
  | 
  | 
  | 
  | 
B_Etat_Arr_Prog  | not activated  | activated  | 417  | 
  | bat  | bat  | 
  | 
  | 
  | 
  | 
  | 
  | 
  | 
  | 
  | 
B_Etat_Lim_Groupe  | not activated  | activated  | 419  | 
  | bat  | bat  | 
  | 
  | 
  | 
  | 
  | 
  | 
  | 
  | 
  | 
B_Etat_IBat_Aux  | not activated  | activated  | 41A  | 
  | bat  | bat  | 
  | 
  | 
  | 
  | 
  | 
  | 
  | 
  | 
  | 
B_Etat_Egal_Bat  | not active  | active  | 41B  | 
  | bat  | bat  | 
  | 
  | 
  | 
  | 
  | 
  | 
  | 
  | 
  | 
B_Etat_Groupe  | not activated  | activated  | 41E  | 
  | yes  | yes  | 
  | 
6739389EN/FB - Page 31