6000 installation manual
1
1
46
46
Download
46 pages, 1.41 Mb
6739381EN/
Installation manual
Single-unit UPS
Modular UPS
Parallel UPS with SSC
Frequency converters
Static Switch Cubicle
MGE
TM
Galaxy
TM
6000
50, 60 Hz
250 - 600 kVA
Contents
Main
MGETM GalaxyTM 6000
Page
Contents
Characteristics
Installation
Appendix
Characteristics
Characteristics common to all cubicles
Rectifier-inverter cubicles
Static Switch cubicles
External maintenance bypass cubicles
"Pack Advance" cubicles
Electrical parameters for selecting protective devices
Electrical parameters for determining cable cross-sections
Heat losses
Page
Page
Installation
(to be carried out by qualified personnel only) Handling Positioning the cubicles
Floor loads (figure 5)
Cubicle layout on false floor or normal floor
front
rear
Power circuit wiring diagrams
-
Diagram for a frequency converter with batteries
+-+-
Fig. 13
mains 2
Diagram for a frequency converter without batteries
-+-
mains 2
Fig. 14
mains 1
mains 2
Fig. 15
Connection of power circuits
160kVA to 400kVA modular UPS rectifier-inverter cubicle
rear
mains 1, mains 2 and load:
600 kVA single-unit UPS cubicles (see the appendix).
terminals and 13 mm diameter holes.
250kVA to 450kVA frequency converter or parallel UPS with SSC rectifier-inverter cubicle
rear
mains 1 and load:
600kVA parallel UPS cubicles (see the appendix).
terminals and 13 mm diameter holes.
Page
500kVA modular UPS rectifier-inverter cubicle
mains 1: 450 mm ; mains 2 and load: 337 mm ; battery: 385 mm ; remote relay board:
1030 mm.
mains 1:
to 50 X 10 mm copper terminals and 12,6 mm diameter holes, and gudgeon 10 mm diameter;
Page
500/800kVA Static Switch Cubicle
mains 2: 1050 mm max.; inverter outputs and load: 570 mm; remote relay board: 1190 mm max.
500kVA Static Switch Cubicle: Cables connected by lugs to 80 x 5 mm
800kVA Static Switch Cubicle: Cables connected by lugs to 80 x 8 mm
rear
1200kVA Static Switch Cubicle
Cables connected by lugs to 80 x 8 mm copper terminals and 14 mm diameter
mains 2: 1310 mm; inverter outputs: 550 mm; load: 850 mm; remote relay board: 570 mm max.
rearfront
Page
Page
Connection of "Media Contacts 9" standard auxiliary circuits
-
Connection of auxiliary circuits on the remote relay board
Fig. 16
recommended cable cross-section:
Connections between cubicles
Emergency shutdown
Connection to battery circuit breaker QF1
(modular UPSs or parallel UPSs with SSC)
Connections between APOZ boards
Connections between ACPZ boards (frequency converters or parallel UPSs with SSC)
Connections between MISI boards (modular UPSs)
Connections between rectifier-inverter cubicles and external maintenance bypass cubicle
Fig. 22
Connection of "Media Contacts 15" additional auxiliary circuits (option) (figure 22)
recommended cable cross-section:
1 mm2;
the male connectors that fit the
female connectors on the board (XR5 to XR9) are supplied;
Connection of the battery "Temperature Monitor" (optional)
BC
+
BC+ BC
12
"Temperature Monitor" installation in a APC by Schneider Electric battery cubicle
"Temperature Monitor" installation in a battery room
Link to an IBM AS/400 computer
Connections:
Connection of the "LED" remote indications unit
Connection of "Tele Monitor" remote control and indication unit
Final installation steps
Configuration of the AS/400
Appendix
Mains 2 line protection
Cubicle mounting and connection for 600kVA UPSs
Cubicle mounting
Internal connections between cubicles
rearfront
Connection of power and auxiliary circuits
Left cubicle of 600kVA single-unit or parallel UPS with SSC
Cables connected by lugs to 100 x 8 mm
mains 1: 450 mm; battery: 480 mm.
Page 38
Right cubicle of a 600kVA single-unit UPS
Cables connected by lugs to 100 x 8 mm
mains 2 and load: 430 mm;
rear front
Cables connected by lugs to 100 x 8mm
Right cubicle of a 600kVA parallel UPS with SSC
copper terminals and 13 mm diameter holes.
mains 2 and load: 430 mm;
Cubicle mounting and connection for 2000kVA Static Switch Cubicle
Cubicle mounting
Internal connections between cubicles
rear
front
Cables connected by lugs to 5 x (5 x 100) mm
copper terminals and 16 mm diameter holes.
inverter outputs : 700 mm remote relay board: 500 mm.
Left cubicle of a 2000kVA Static Switch
rear front
Details of earthing connections in the various cubicles
250 to 400kVA rectifier-inverter cubicle
inverter input
inverter input
450 - 500kVA rectifier-inverter cubicle
120 to 1200kVA Static Switch Cubicles
input
600kVA rectifier-inverter cubicle
input
inverter input inverter
2000kVA Static Switch Cubicles
input
"Tele-Monitor" unit