APC 6000 Number Total UPS Mains 2 or load, Line current, KVA Inverters Amps Copper

Models: 6000

1 46
Download 46 pages 29.39 Kb
Page 9
Image 9

Characteristics (cont.)

The table opposite serves as an example for an installation with up to four modular UPSs with an external maintenance bypass.

for installations with redundant units, take into account only the units required to supply the load power (e.g. for an installation made up of 3 parallel-connected rectifier-inverter cubicles, one being redundant, only 2 units are used to determine the currents on the maintenance bypass line and the load, and the cross- sectional areas of cables);

this table has been drawn up for rated phase-to-phase Mains 2 and load voltages of 415V and full rated load with a power factor of 0.8. For voltages of 380 or 400V, multiply the indicated currents by 1.09 and 1.04 respectively, then modify the cable cross-sections accordingly if necessary.

The cable cross-sections in this table are for the parts illustrated in bold on the following block diagrams (installation example, figure 3);

important. In an installation with an external maintenance bypass, the power cables between each UPS and the upstream protection devices must be the same length. The same holds for the power cables between each UPS cubicle and the external maintenance bypass.

Parameters for connection of the external maintenance bypass circuit and the load in an installation comprising modular UPSs

rated inverter

number of

total UPS

Mains 2 or load

cable cross-section

output

parallel-connected

rated output

line current

(1) in mm2

 

in kVA

inverters

in kVA

in Amps

Copper

 

Aluminium

250

2

500

722

2 x 185

 

2 x 300

 

3

750

1082

3 x 300

 

4 x 240

 

4

1000

1444

4 x 240

 

4 x 400

300

2

600

866

2 x 240

 

4 x 185

 

3

900

1299

4 x 240

 

4 x 400

 

4

1200

1732

Please consult us*

400

2

800

1154

4 x 185

 

4 x 300

 

3

1200

1731

Please consult us*

 

4

1600

2308

Please consult us*

450

2

900

1299

4 X 240

 

4 x 400

 

3

1350

1948

Please consult us*

500

2

1000

1444

4 X 240

 

 

4 x 400

 

3

1500

2166

Please consult us*

(1) cable cross-sections are given for copper

NF C 15-100 authorizes a maximum of 4

conductors of the U1000 R02V type. They are

 

 

 

 

 

calculated according to permissible temperature

cables per phase.

 

rise and allow for line voltage drops over a

 

maximum length of 100 m. For greater lengths,

 

the cross-sections should be chosen to limit

 

voltage drops to 3%.

 

Installation comprising modular UPSs with an external maintenance bypass

maintenance Bypass cubicle

mains 1

inverter 1

 

 

 

mains 2

 

 

mains 1

inverter 2

load

 

mains 2

 

 

mains 1

inverter 3

 

 

 

mains 2

 

 

Fig. 3

6739381EN/

Page 9
Image 9
APC 6000 installation manual Number Total UPS Mains 2 or load, Line current, KVA Inverters Amps Copper