Installation (cont.)

Connection of "Media Contacts 9" standard auxiliary circuits (figure 16)

The standard auxiliary circuits of the rectifier-inverter and Static Switch Cubicles are connected to the remote relay board by 4 connectors (see the location of this board in the figures of the previous section).

recommended cable cross-section: 1 mm2 (use a shielded cable to connect the battery cell);

the male connectors that fit the female connectors on the board (XR1 to XR4) are supplied;

the contacts are volt-free and are shown in the diagram under the following conditions: UPS on, contact at rest;

contact breaking capacity: 250V, 5A.

Connection of auxiliary circuits on the remote relay board

remote

1

12

1

12

1

12

1

12

 

 

 

 

 

 

 

 

 

 

 

 

 

relay board

 

XR1

 

 

 

XR2

 

XR3

 

XR4

connector XR1

 

 

output signals:

 

 

 

 

 

 

 

 

 

connector XR2

connector XR3

+12V

24 V DC

-12V

connector XR4

temperature signal

power -12V

supply +12V earth

earth

1

2

3

4

5

6

7

8

9

10

11

12

1

2

3

4

5

6

7

8

9

10

11

12

1

2

3

4

5

6

7

8

9

10

11

12

1

2

3

4

5

6

7

8

9

10

11

12

low battery shutdown warning (1)

low battery shutdown warning (1)

load on battery (1)

load on battery (1)

output signals:

load on inverter (2)

load on inverter (2)

general alarm (2)

general alarm (2)

input or output signals:

maintenance position (2)

shielded cable (2 twisted

telephone pairs)

maintenance position (2)

battery circuit breaker QF1 opening command (1)

input or output signals:

battery room ventilation fault (1)

and/or harmonics filter temperature fault

connection with the optional electronic board for measuring battery temperature (1)

emergency shutdown button contact (jumper if not used) (1)

(1)for:

single-unit UPS cubicle,

modular UPS cubicle,

parallel UPS cubicle with SSC.

(2)for:

single-unit UPS cubicle,

modular UPS cubicle,

parallel UPS cubicle with SSC,

Static Switch cubicle.

battery cubicle (1)

XR1 terminal block

3

battery circuit

breaker QF1

4

opening command

 

1

battery circuit

 

breaker QF1

2

closing command

 

harmonics filter cubicle

XR1 terminal block

1 temperature

2monitoring of the harmonics filter inductor

Fig. 16

Page 26 - 6739381EN/JD

Page 26
Image 26
APC 6000 installation manual Connection of auxiliary circuits on the remote relay board, XR1 XR2 XR3 XR4