Installation (cont.)

Connection to battery circuit breaker QF1

Connect the cable from connector XR3 (pins 7 to 12) of the rectifier-inverter cubicle remote relay board to connector XR1 of the battery cubicle containing battery circuit breaker QF1.

Emergency shutdown

The UPS emergency shutdown function is generally wired to a "mushroom-head" type emergency off button.

Important:

In the case of a complex installation with a number of units, there should only be one emergency shutdown pushbutton and this pushbutton must interrupt all the active conductors of all the units.

For the same reason, it is essential for the pushbutton to open the upstream mains 1, mains 2, and external maintenance bypass line protective

circuit breakers.

Each type of unit (UPS and Static Switch Cubicle) must have an independent, volt-free contact connected to the emergency shutdown pushbutton. This pushbutton must therefore have as many contacts as there are units in the installation, as well as the contact or contacts required to open the upstream mains 1 and 2 protective circuit breakers. The emergency shutdown pushbutton turns off the rectifier-chargers and inverters and opens the battery circuit breakers. The emergency shutdown signal will be cleared when the emergency shutdown

pushbutton contact has been reset. The emergency shutdown pushbutton should not be connected to the Static Switch Cubicle since the pushbutton opens the circuit breaker protecting the upstream circuit (mains 2) and the Static Switch Cubicle is therefore no longer powered (inverters off and mains 2 down).

Connections between cubicles

(modular UPSs or parallel UPSs with SSC)

On modular UPSs, interconnections are made on the APOZ (figure 17) and MISI (figures 19 to 21) boards in the UPS cubicles (see the layout of the boards in the figures in the previous section).

For parallel UPSs with a centralised SSC, interconnections are made on the APOZ boards in the UPS cubicles (figure 17) and the ACPZ boards (see the layout of the boards in the figures in the previous section) in the SSC (figure 18).

Connections between APOZ boards

these connections are made using the ribbon cables supplied;

the purpose of the connection is to make a loop: connector XM137 of the APOZ board of one UPS being connected to connector XM136 of the APOZ board of the next UPS and so on until the first board is returned to.

Important:

Outside the cubicles, group the APOZ inter-board and ACPZ or MISI inter- board connections with the inter-cubicle auxiliary connections, and separate this assembly from the power cables.

Connections between rectifier-inverter cubicles

APOZ board rectifier-inverter 1

XM137

XM136

APOZ board rectifier-inverter 2

ribbon cables supplied

XM137

XM136

APOZ board rectifier-inverter 3

XM137

XM136

Fig. 17

6739381EN/

Page 27
Image 27
APC 6000 installation manual Connections between cubicles, Connection to battery circuit breaker QF1, Emergency shutdown