Installation (cont.)

"Temperature Monitor" installation in a APC by

Installing the "Temperature Monitor" in a battery cubicle

Schneider Electric battery cubicle

The "Temperature Monitor" is fitted on mounting brackets inside the left-hand door of the battery cubicle containing circuit breaker QF1 (see figure 25). The unit is self-adhesive and is secured simply by pressing it against the door:

before mounting the unit, break the

knock-out in its base plate provided for

feeding through the connecting cable;

clean the mounting location on the

door using isopropyl alcohol or heptane

to obtain a clean, dry adhesion surface

(comply with supplier safety

recommendations for handling

solvents);

it is essential, for correct temperature

sensor operation, for the unit to be

positioned as shown in figure 25 ("on"

light in the top left hand corner and

cable fed through from the right-hand

side);

"on" light

self-adhesive

mounting brackets

tie the cable to the cubicle upright

battery cubicle

tie

the

cable

 

 

 

QF1

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

to the

cubicle

 

 

 

 

 

upright

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

to rectifier-inverter

firm pressure is required to ensure

that the unit is bonded over the full

adhesive surface;

the door should be at a temperature

of at least 10°C;

after installation, fold up the

mounting bracket tabs to fully secure

the unit;

tie the connecting cable to the

cubicle upright so that it does not pull

on the unit.

Fig. 25

"Temperature Monitor" installation in a battery room

The "Temperature Monitor" should be secured against a wall or any vertical support:

choose a location near the batteries and away from draughts which adversely affect the accuracy of temperature measurements;

position the unit correctly ("on" light in the top left hand corner and cable fed through from the right-hand side);

use the holes provided in the base plate to screw the unit to the vertical support (see figure 26);

unless the connecting cable runs on the surface, break the knock-out in the unit base plate provided for cable entry;

secure the cable by suitable means so that it does not pull on the unit.

"Temperature Monitor" base

 

oblong holes

 

for fastening screws

board

knock-out for

 

lateral cable

 

entry

oblong holes

for fastening screws

dimensions of the "Temperature Monitor": 75 x 75 x 21 mm

Fig. 26

Page 32 - 6739381EN/JD

Page 32
Image 32
APC 6000 Temperature Monitor installation in a APC by, Schneider Electric battery cubicle, Temperature Monitor base