Mains 2 line protection

The rating of the mains 2 line upstream protection circuit-breaker must be chosen:

to protect the static switch thyristors with respect to maximum permissible currents. Refer to the table opposite for a 400V mains 2 voltage;

to ensure discrimination with respect to the UPS output fuses (refer to fuse time-current curves below) and to the downstream protective devices.

rated inverter output

maximum permissible current

(kVA)

 

250 to 300

10 In for 20 ms

400 to 450

13 In for 20 ms

500 to 600

27 In for 20 ms