Installation (cont.)

160kVA to 400kVA modular UPS rectifier-inverter cubicle

cross-section AA

front view

front

air extraction

rear

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

A

 

 

 

rectifier

 

inverter

 

inverter

 

 

inverter

 

 

 

charger

 

stack

 

stack

 

 

stack

 

 

 

 

 

 

 

 

 

 

 

card

 

card

XR1

XR8

INTZ

 

 

XM12

 

 

cage

 

XR9

board

 

 

 

air admission

 

cage

 

XM7

 

 

 

 

 

XR2

XR5

 

 

XM11

 

 

 

 

 

 

XM6

 

 

 

 

XM136

APOZ board

XR3

XR6

 

 

XM10

 

 

 

 

 

 

 

 

 

XM137

 

XR7

 

 

 

 

 

 

 

XR4

 

XM5

 

 

 

 

 

 

 

 

 

 

 

 

 

 

remote relay

 

FHCZ

static

 

MISI board

 

 

 

 

switch

 

 

 

 

 

 

board

 

board

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

additional remote relay board

 

 

 

 

 

 

 

 

(optional)

 

 

Q4S

Q3BP

 

Q5N

 

 

 

Q1

 

 

 

 

 

 

 

 

 

 

 

 

 

 

transformer

 

on

 

off

on

off

on

off

on

 

 

 

 

 

 

 

off

 

 

 

 

 

 

 

mains 1,

 

 

 

 

 

 

 

 

 

 

mains 2,

 

 

 

 

 

 

 

 

 

 

load

 

 

L1 L2 L3

 

 

 

N L1L2 L3

N L1 L2 L3

battery

 

 

 

 

 

 

 

mains 1

L+

L

 

mains 2

load

 

 

 

 

 

 

 

 

 

air admission

 

 

 

battery

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

cable tie bar

 

 

 

 

 

 

 

 

 

 

connection

 

 

 

 

 

 

 

 

A

 

from below

 

spacing

 

 

cable

 

 

spacing

 

trough (if applicable)

 

uprights

 

 

tie bar

 

 

uprights

 

 

 

power cable routing

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

via the bottom

 

 

 

 

 

Cables connect by lugs:

mains 1, mains 2 and load:

to 40 X 4 mm copper terminals and 13 mm diameter holes;

battery:

250 to 300 kVA UPSs:

to 65 X 4 mm copper terminals and 13 mm diameter holes,

400 kVA UPSs: to 80 X 5 mm copper terminals and 13 mm diameter holes.

Height of connections relative to floor:

mains 1, mains 2 and load: 440 mm;

battery: 390 mm;

remote relay board: 1030 mm.