Characteristics (cont.)

Rectifier-inverter cubicles

The parameters given in the table opposite can be used to determine the required rating of a single-unit or modular UPS, a frequency converter, or a parallel UPS with SSC.

Characteristics of rectifier-inverter cubicles

 

 

 

 

 

 

rated

cubicle

cubicle

cubicle

maximum

 

inverter

width W

height H

depth D

weight

 

output

in mm (1)

in mm

in mm

in kg

 

in kVA

 

 

 

 

 

250

1600

1900 ± 10

840

1650

 

300

1600

1900 ± 10

840

1650

 

400

1600

1900 ± 10

840

2030

 

 

 

 

 

 

 

450

1600

2000 ± 10

840

2070

 

 

 

 

 

 

 

500

1600

2000 ± 10

840

2205

 

600

3600

1900 ± 10

840

3500

 

 

 

 

 

 

 

(1)25 mm must be added on each side to the indicated cubicle width, i.e. 50 mm in all per cubicle. This applies to all cubicle installation cases.

When installing several cubicles, allow for a tolerance of 0/+3mm per metre.

Static Switch cubicles

 

 

 

 

 

 

 

Characteristics of Static Switch Cubicles

 

 

 

 

 

 

 

 

 

 

 

 

rated

cubicle

cubicle

cubicle

maximum

heat

 

 

SSC

width W

height H

depth D

weight

losses (2)

 

 

output

in mm (1)

in mm

in mm

in kg

 

 

 

in kVA

 

 

 

 

in kW

in cal./s

 

500

1000

1900 ± 10

840

350

2.9

696

800

1000

1900 ± 10

840

500

3.7

888

 

1200

1600

1900 ± 10

840

1000

< 0.5

< 120

 

2000

2450

1900 ± 10

840

1710

< 0.5

< 120

(1)25 mm must be added on each side to the indicated cubicle width, i.e. 50 mm in all per cubicle. This applies to all cubicle installation cases.

When installing several cubicles, allow for a tolerance of 0/+3mm per metre.

External maintenance bypass cubicles

Characteristics of external maintenance bypass cubicles

(Modular UPS with external maintenance bypass)

rated

cubicle

cubicle

cubicle

maximum

 

bypass

width W

height H

depth D

weight

in kVA

in mm (1)

in mm

in mm

in kg

 

 

 

 

 

 

1200

1200

1900 ± 10

840

450

 

 

 

 

 

 

 

(1)25 mm must be added on each side to the indicated cubicle width, i.e. 50 mm in all per cubicle. This applies to all cubicle installation cases.

When installing several cubicles, allow for a tolerance of 0/+3mm per metre.

"Pack Advance" cubicles

Characteristics of "Pack Advance"Cubicles

 

 

 

 

 

 

 

 

rated

cubicle

cubicle

cubicle

maximum

heat

 

 

SSC

width W

height H

depth D

weight

losses (2)

 

 

output

in mm (1)

in mm

in mm

in kg

 

 

 

in kVA

 

 

 

 

in kW

in cal./s

 

300

400

1900 ± 10

840

335

2.9

696

 

400

400

1900 ± 10

840

440

3.7

888

 

450

400

1900 ± 10

840

440

< 0.5

< 120

 

 

 

 

 

 

 

 

 

(1)25 mm must be added on each side to the indicated cubicle width, i.e. 50 mm in all per cubicle. This applies to all cubicle installation cases.

When installing several cubicles, allow for a tolerance of 0/+3mm per metre.

6739381EN/

Page 5
Image 5
APC 6000 Rectifier-inverter cubicles, Static Switch cubicles, External maintenance bypass cubicles, Pack Advance cubicles