Fig. 22

Connection of "Media Contacts 15" additional auxiliary circuits (option) (figure 22)

The additional auxiliary circuits of the

rectifier-inverter and Static Switch

Cubicles are connected to additional

remote relay board by means of the 4

connectors (see location of this board

in the figures of the "connection of

power circuits" section).

recommended cable cross-section:

1 mm2;

the male connectors that fit the

female connectors on the board

(XR5 to XR9) are supplied;

the contacts are volt-free and are

shown in the diagram under the following

conditions: UPS on, contact at rest;

ACPZ board of the Static Switch Cubicle

contact breaking capacity: 250V, 5A.

Note:

In a parallel-connected UPS installation

the "load" and "mains 2" signals are

provided by the Static Switch Cubicle.

112
XR7
additional remote
relay board
connector XR5
(option)
output signals:
connector XR6
(option)
connector XR8
(option)
input signals:
connector XR7
(option)
110
XR8
110
XR9
112
XR6
112
XR5
connector XR9
(option)
1
2
3
4
5
6
7
8
9
10
11
12
overload (2)
inverter function fault (1)
overload (2)
inverter function fault (1)
rectifier-charger operating (1)
rectifier-charger function fault (1)
1
2
3
4
5
6
7
8
9
10
11
12
rectifier-charger operating (1)
rectifier-charger function fault (1)
transfer to Mains 2 inhibited (3)
transfer function fault (2)
1
2
3
4
5
6
7
8
9
10
11
12
transfer to Mains 2 inhibited (3)
transfer function fault (2)
transfer to Mains 2 inhibited (4) (5)
desynchronization with Mains 2 (3)
1
2
3
4
5
6
7
8
9
10
transfer to Mains 2 with interruption inhibited (4) (5)
battery charge current limiting (1)
gradual rectifier-charger shutdown (1)
current limiting on generator power (1)
1
2
3
4
5
6
7
8
remote inverter on (1)
auxiliary signal (2)
remote inverter off (1)
(1) for:
single-unit UPS cubicle,
modular UPS cubicle,
parallel UPS cubicle with SSC.
(2) for:
single-unit UPS cubicle,
modular UPS cubicle,
parallel UPS cubicle with SSC,
Static Switch cubicle.
(3) for:
single-unit UPS cubicle,
modular UPS cubicle,
Static Switch cubicle.
(4) in modular UPSs, these functions are
available via the "auxiliary information" contact
(connector XR9, terminals 7-8).
(5) for:
single-unit UPS cubicle,
Static Switch cubicle.
Installation (cont.)