Appendix (cont.)

Left cubicle of a 2000kVA Static Switch

cross-section AA

air extraction

front

air

admission

air

admission

connection

from below

trough (if applicable)

front view

rear

 

 

 

 

 

A

 

 

 

K2S switch

 

 

 

 

 

 

 

 

 

ACPZ board

 

 

 

 

 

 

XM127 to 132

 

 

 

 

 

 

remote

N

L1

L2

L3

card cage

 

relay

 

board

 

 

 

 

 

 

XR7

XR4

 

 

inverter outputs

XR6

 

 

XR3

 

 

 

 

 

 

 

 

 

 

XR5

 

 

 

 

 

XR2

 

 

 

 

 

 

remote

 

 

 

 

XR9

XR1

 

 

 

 

XR8

relay

 

 

 

 

 

board

 

 

 

 

 

 

 

 

 

 

 

A

 

 

 

 

spacing

 

 

 

 

 

 

uprights

 

 

 

power cable routing via the bottom

Cables connected by lugs to

5 x (5 x 100) mm copper terminals and

16 mm diameter holes.

Height of connections relative to floor:

inverter outputs : 700 mm

remote relay board: 500 mm.

Page 42 - 6739381EN/JD

Page 42
Image 42
APC 6000 installation manual Left cubicle of a 2000kVA Static Switch, XR6 XR3 XR5 XR2, XR9 XR1 XR8