Characteristics

Characteristics common to all cubicles

After moving them to their installation location on their pallets,

MGETM GalaxyTM 6000 cubicles can be moved short distances using a forklift or pallet-mover when the front, rear and side base panels are not mounted. The forks can be inserted from all four sides into 100 mm

+/– 10 mm high openings;

the unadjusted cubicle height (H) is 1900/2000 mm; after lifting the cubicle, the height can be adjusted +/– 10 mm by screwing in or out the four feet;

the bearing surface corresponds to the area of the four cylindrical foot pads (60 mm diameter) positioned in each corner of the cubicle;

the cubicle depth (D) is 840 mm (800 mm without doors and panels);

operating temperature range for rectifier-inverter, frequency converter or Static Switch Cubicles: 0°C to 35°C at rated output (40°C for a maximum of

8 hours) and 30°C maximum for overload conditions. Operation outside the specified temperature range will reduce service life;

relative humidity: 95% maximum;

maximum operating altitude without derating: 1000 m;

connection via the bottom for

rectifier-inverter cubicles, or via the top with the addtion of an optional duct that can be installed on the right side of the cubicle. The auxiliary and Static Switch Cubicles are designed for connections via the top or bottom.

the connection cables may be run in three ways:

in a trench running under the cubicles,

MGETM GalaxyTM 6000 UPS: example of a rectifier-inverter cubicle

H

L

P

under a false floor,

on the floor under the cubicles, in the free space equal to the height of the feet; in this case the cables should be run side by side to avoid blocking the flow of air for ventilation.

the intercubicle connection cables are not supplied (except for the wires for auxiliary interconnections);

normally the cubicles do not have to be secured to the floor; the footpads nevertheless have holes with an average depth of 12 mm designed for the fitting of M16 anchor bolts;

the cubicle doors are secured by Ronis locks (key 405).