Installation

(to be carried out by qualified personnel only)

Handling

Unpacked cubicles may be moved using a forklift from the front or from the back. Distances must not exceed a few meters.

Positioning the cubicles

(for 600 kVA UPSs, see the appendix as well)

prior to moving the cubicles to their final position, remove the packing material and withdraw the base panels from the space on the side created by the spacing uprights. The panels will be installed at the end of the installation procedure;

spacing uprights on the sides of the cubicles create a 50 mm clearance when cubicles are positioned next to each other, enabling users to open the doors (see figure 4). If a cubicle is installed next to a wall, leave additional space so that the cubicle is 50 mm from the wall;

when the spacing uprights are not required (cubicles are not positioned next to a wall or another cubicle), they may be removed:

loosen the four screws securing the upright,

lift the upright and pull it free,

replace the long gold-coloured screws with the black screws supplied in a bag attached to the cable terminals in the cubicle;

adjust the height of the feet until the first cubicle is perfectly vertical; adjust the feet of the subsequent cubicles so that the all the doors are perfectly aligned.

Side clearances provided by the spacing uprights

rear

 

 

 

50

50

 

cubicle 1

cubicle 2

front

spacing uprights

spacing uprights

of cubicle 1

of cubicle 2

Fig. 4