APC 6000 user manual Static Switch, Main indicators of system operations

Models: 6000

1 38
Download 38 pages 11.72 Kb
Page 27
Image 27

Static Switch (continued)

Main indicators of system operations

Normal

: charge alimentée par l'onduleur

bit 4C4 = 1

Danger

:

charge non alimentée par l'onduleur

bit 4C6 = 1

Downgraded

:

anomalie de fonctionnement

bit 4C5 = 1

 

 

ou défaut d'environnement

 

 

 

 

 

Operating modes

The following section describes the different states of a Static Switch cubicle and the addresses of the bits in the system data array.

Normal operation

Load on Mains 2

Load on bypass

Normal:

Danger:

Downgraded: Q5N closed: Q3BP open: Q4S closed: SS open:

K2S open (if available): Inverters connected to load:

Normal:

Danger:

Downgraded:

Q5N closed:

Q3BP open:

Q4S closed:

SSclosed (if K2S not available): K2S closed (if available): Inverters not connected to load:

Normal:

Danger:

Downgraded: Q5N open: Q3BP closed: Q4S indifferent: CS indifférent: SS indifferent:

Inverter connected indifferent:

bit 4C4 = 1 bit 4C6 = 0

bit 4C5 = malfunction dependent bit 498 = 1

bit 497 = 0 bit 496 = 1 bit 499 = 0 bit 494 = 0 bit 4AE = 1

bit 4C4 = 0 bit 4C6 = 1

bit 4C5 = X (N/A) bit 498 = 1

bit 497 = 0 bit 496 = 1 bit 499 = 1 bit 494 = 1 bit 4AE = 0

bit 4C4 = 0 bit 4C6 = 1

bit 4C5 = X (N/A) bit 498 = 0

bit 497 = 1

bit 496 = X (N/A) bit 499 = X (N/A) bit 494 = X (N/A) bit 4AE = X (N/A)