APC 6000 user manual Main status bits UPS operating information, Operating modes

Models: 6000

1 38
Download 38 pages 11.72 Kb
Page 22
Image 22

Unitary UPS (continued)

Main status bits (UPS operating information)

Normal

: inverter powers load and full backup

bit 4C4 = 1

 

 

time available

 

Danger

: inverter does not power load

bit 4C6 = 1

Downgraded

:

malfunction or environment fault

bit 4C5 = 1

Load on battery

:

fonctionnement en autonomie

bit 4C7 = 1

Operating modes

The following section describes the different states of a

MGETM GalaxyTM 6000 UPS and the addresses of the bits in the system data array.

Normal operation

Load on battery

Normal:

bit 4C4 = 1

Danger:

bit 4C6 = 0

Downgraded:

bit 4C5 = malfunction dependent

Load on battery:

bit 4C7 = 0

Q1 closed:

bit 40E = 1

Rectifier/charger on:

bit 408 = 1

QF1 closed:

bit 400 = 1

Inverter connected:

bit 484 = 1

Q5N closed:

bit 498 = 1

Q3BP open:

bit 497 = 0

Q4S closed:

bit 496 = 1

SS open:

bit 499 = 0

K2S open (if available):

bit 494 = 0

Normal:

bit 4C4 = 1

Danger:

bit 4C6 = 0

Downgraded:

bit 4C5 = malfunction dependent

Load on battery:

bit 4C7 = 1

Q1 indifferent:

bit 40E = X (N/A)

Rectifier/charger off:

bit 408 = 0

QF1 closed:

bit 400 = 1

Inverter connected:

bit 484 = 1

Q5N closed:

bit 498 = 1

Q3BP open:

bit 497 = 0

Q4S closed:

bit 496 = 1

SS open:

bit 499 = 0

K2S open (if available):

bit 494 = 0

Page 22 - 6739389EN/FB

Page 22
Image 22
APC 6000 user manual Main status bits UPS operating information, Operating modes, Normal operation Load on battery