Operation: Operation Procedures

Set the upstream mains power to the OFF or LOCKED OUT position. If the UPS has a dual mains supply, set both supplies to the OFF or LOCKED OUT position.

Electrical Hazard: Follow proper Lockout/Tagout procedures to remove access to the unit and physically label the unit as intentionally out of service.

How to turn the load on/off using the display interface

 

 

 

 

 

 

 

 

UPS

Alarms

 

 

 

 

 

 

Power Dist

Log

 

 

 

Switch Gear

Admin

 

 

 

Environment

Help

 

 

 

 

 

 

 

 

 

 

Turn UPS Off

Reboot UPS

UPS Into Bypass

UPS To Sleep

Press

Press

UPS Power Control

UPS Status

UPS Tests & Diags

UPS Configuration

Press

How to put the UPS in maintenance bypass operation

Use the display to put the UPS into bypass.

 

 

 

 

 

 

 

 

UPS

Alarms

 

 

 

 

 

 

 

 

 

 

 

 

Power Dist

Log

 

 

 

 

Switch Gear

Admin

 

 

 

 

Environment

Help

 

 

 

 

 

 

 

 

 

 

 

 

Turn UPS Off

Reboot UPS

UPS into Bypass

UPS to Sleep

Putting UPS Into Bypass, please wait...

Press

Press

UPS Power Control

UPS Status

UPS Tests & Diags

UPS Configuration

Confirm:

UPS into Bypass?

NO, ABORT

YES, Into Bypass

UPS is now in bypass, press any key to return to previous menu

Press

Press

Confirm the transfer into bypass is complete.

Note: The H3 LED next to the Q3 switch on the PDU-XR will illuminate, indicating that it is safe to operate the Q3 switch.

Set the Q3 switch on the PDU-XR to the ON position.

Note: The H2 LED beside the Q2 switch will illuminate, indicating that it is safe to operate the Q2 switch.

990-3015-001

Symmetra PX 160 kW 400 V Operation

9

Page 15
Image 15