Operation: Operation Procedures
990-3015-001 Symmetra PX 160 kW 400 V Operation 9
Set the upstream mains power to the OFF or LOCKED OUT position. If the UPS has a dual mains

supply, set both supplies to the OFF or LOCKED OUT position.

Electrical Hazard: Follow proper Lockout/Tagout procedures to remove access to the

unit and physically label the unit as intentionally out of service.

How to turn the load on/off using the display interface

How to put the UPS in maintenance bypass operation

Use the display to put the UPS into bypass.

Confirm the transfer into bypass is compl et e.

Note: The H3 LED next to the Q3 switch on the PDU -XR will illuminate, indicating that

it is safe to operate the Q3 switch.

Set the Q3 switch on the PDU-XR to the ON position.

Note: The H2 LED beside the Q2 switch will illuminate, indicating that it is safe to

operate the Q2 switch.