Operation: Operation Procedures

Set the Q2 switch on the PDU-XR to the OFF position.

Turn the UPS off using the display.

 

Press

UPS

Alarms

 

UPS Power Control

Power Dist

Log

 

UPS Status

Switch Gear

Admin

 

UPS Tests & Diags

Environment

Help

 

UPS Configuration

Press

Turn UPS Off

Reboot UPS

UPS into Bypass UPS to Sleep

Turn UPS Off With

Server Notification?

>NO, ABORT

>YES, Turn UPS Off

Press

Notify PowerChute?

Cancel

Yes, Notify Servers

No, Don’t Notify

Turning UPS off,

please wait...

Press

Set the Q1 switch on the PDU-XR to the OFF position.

Set the Q5 switch on the PDU-XR to the OFF position.

Set the UPS SYSTEM ENABLE switch to the OFF position.

Set the DC DISCONNECT switch on all of the XR Battery enclosures and the PDU-XR to the OFF position.

10

Symmetra PX 160 kW 400 V Operation

990-3015-001

Page 16
Image 16
APC SYCFXR9, PDUM160H-B, SY160K160H manual YES, Turn UPS Off