Modular Distribution fault list

The display interface will identify the number of the power distribution module that has caused an alarm or warning.

Display Message

Meaning

Corrective Action

 

 

 

High Module Current

The high module current

Evaluate the threshold setting. If necessary, adjust

 

threshold has been exceeded.

it for your situation.

 

 

 

High Subfeed Current

The high subfeed current

Evaluate the threshold setting. If necessary, adjust

 

threshold has been exceeded.

it for your situation.

 

 

 

Low Module Current

The low module current

Evaluate the threshold setting. If necessary, adjust

 

threshold has been exceeded.

it for your situation.

 

 

 

Low Subfeed Current

The low subfeed current

Evaluate the threshold setting. If necessary, adjust

 

threshold has been exceeded.

it for your situation.

 

 

 

Maximum Module Current

The maximum module current

Evaluate the threshold setting. If necessary, adjust

 

threshold has been exceeded.

it for your situation.

 

 

 

Maximum Subfeed Current

The maximum subfeed current

Evaluate the threshold setting. If necessary, adjust

 

threshold has been exceeded.

it for your situation.

 

 

 

Minimum Module Current

The minimum module current

Evaluate the threshold setting. If necessary, adjust

 

threshold has been exceeded.

it for your situation.

 

 

 

Minimum Subfeed Current

The minimum subfeed current

Evaluate the threshold setting. If necessary, adjust

 

threshold has been exceeded.

it for your situation.

 

 

 

Modular Distribution

Communication has been lost

Check the communication cables to ensure they

Communication

with the modular distribution

are properly connected. Contact APC Customer

 

breakers.

Support.

 

 

 

Module Breaker Open

A modular circuit breaker is

Check the modular circuit breakers to see if one

 

open.

has overloaded. Replace if necessary.

 

 

 

Subfeed Breaker Open

A subfeed circuit breaker is

Check the subfeed circuit breakers to see if one

 

open.

has been over-loaded.

 

 

 