Maintenance: Parts Replacement

How to replace a battery module

Use two people to lift components weighing between 18–32 kg/40–70 lb.

Holding the handle, gently lift the battery unit and pull it halfway out. A lock mechanism prevents it from being pulled all the way out.

Release the lock by pushing the battery unit upwards and pull the battery unit all the way out while supporting it

Take the replacement battery unit and push it into the system.

Note: Allow for a 24-hour recharging period of the batteries after system start-up/battery replacement for battery monitoring data to become fully reliable.

How to replace a power distribution module

Disconnect the power cable from the power distribution module from the extension cable.

Open the locking latch on the module and gently pull it out of the enclosure.

Reverse the procedure to install the new module.