Maintenance: Parts Replacement

How to remove a power module

Use two people to lift components weighing between 18–32 kg/40–70 lb.

1

1

Turn the locking latch down until the arrow points down.

Unscrew the spring-activated knobs on both sides of the module.

Pull the module out of the enclosure as far as the lock mechanism will allow.

Release the lock by pushing the black plastic tab on each side of the module.

Pull the module up and out of the enclosure.

How to install a power module

Reverse the procedure for installation of the replacement module. The display interface will indicate that the system has recognized a new module.

Caution: Secure the locking latch before tightening the spring-activated knobs on the module to ensure that the module makes proper contact in the unit. The power module will not operate unless the locking latch is locked.

990-3015-001

Symmetra PX 160 kW 400 V Operation

17

Page 23
Image 23
APC SY160K160H, PDUM160H-B, SYCFXR9 manual How to remove a power module, How to install a power module