Operation: Operation Procedures
990-3015-001 Symmetra PX 160 kW 400 V Operation 11

How to return to normal operation

Set the DC DISCONNECT switch on all of the XR Battery enclosures and the PDU-XR to the ON
position.
Set the Q1 switch on the PDU-XR or external main tenance bypass panel to the ON position.
Set the Q5 switch on the PDU-XR or external maintenance bypass panel to the ON position.
Set the SYSTEM ENABLE switch on the UPS to the ON position.
Note: Wait approximately 30 seconds for system to start.
Using the display interface, select the follow in g:
Press PressPress Press
UPS Alarms
Power Dist
Switch Gear
Environment
Log
Admin
Help
UPS Control
UPS Status
UPS Tests & Diags
UPS Configuration
Turn UPS On
UPS On Into Bypass UPS Load is ON.