Operation: Operation Procedures

How to return to normal operation

Set the DC DISCONNECT switch on all of the XR Battery enclosures and the PDU-XR to the ON position.

Set the Q1 switch on the PDU-XR or external maintenance bypass panel to the ON position.

Set the Q5 switch on the PDU-XR or external maintenance bypass panel to the ON position.

Set the SYSTEM ENABLE switch on the UPS to the ON position.

Note: Wait approximately 30 seconds for system to start.

Using the display interface, select the following:

UPS

Press

 

Alarms

 

 

Power Dist

Log

 

 

Switch Gear

Admin

 

 

Environment

Help

 

Turn UPS On

Press

 

 

 

 

UPS On Into Bypass

 

UPS Control

UPS Status

UPS Tests & Diags

UPS Configuration

UPS Load is ON.

Press

Press

990-3015-001

Symmetra PX 160 kW 400 V Operation

11

Page 17
Image 17
APC SY160K160H, PDUM160H-B, SYCFXR9 manual How to return to normal operation