22 | Installation (for qualified installers only) |
Facing Requirements
NOTE: The combustible area above the facing must not protrude more than 3/4" from the facing. If it does, it is considered a mantel and must meet the mantel requirements listed in this manual.
Face Dimensions
Face | Height | Width | Bottom of Face | Installation Notes |
|
|
|
|
|
Arched Faces | Flush w base of fireplace | Arched top is | ||
Bungalow, T. of L. | Flush w base of fireplace |
| ||
Vict. Lace | Flush w base of fireplace |
| ||
Looking Glass | Cast face is approx. 2” thick | |||
|
|
|
|
|
Wilmington |
| |||
|
|
|
|
|
Facing Under 1” Thick
Any material that protrudes more than 3/4” in front of the facing is considered a mantel and must meet the mantel requirements in this manual.
NOTE: The facing tucks behind the flanges.
(approx.)
The facing (combustible or
c
Recommended Order of Installation We recommend installing the facing (drywall, tile) under the notch at the front of the fireplace (“a”) - then install the sides and top (“b” and “c”)
a
b
and top of the fireplace.
NOTE The facing tucks under the notch at the front of the fireplace (3/8” above the base of the fireplace).
Facing Over 1” Thick
•Facing that protrudes in front of the face above the face (or within 1/2” of each side) must be made of
NOTE A 3/8" gap above the face is required for face installation and removal.
© Travis Industries | 4040830 |