Mantel Requirements

Installation (for qualified installers only)

27

Mantel Requirements

The combustible area above the facing must not protrude more than 3/4" from the facing. If it does, it is considered a mantel and must meet the mantel requirements listed below.

Use the table below to determine the maximum mantel depth allowed. For example, if a 6” mantel is used, it must be a minimum of 6-1/2” above the face.

Maximum Mantel Depth (b)

0” 1” 2” 3” 4” 5” 6” 7” 8” 9” 10” 11” 12”

 

9”

 

 

8”

 

 

7”

 

Mantel

6”

 

 

 

Height

5”

 

 

 

Above

4”

a

 

Face (a)

3”

 

 

 

 

2”

 

 

1”

 

 

0”

 

b

See “Face Dimensions”

If you have a tapered mantel, measure the mantel height at the point where it protrudes 3/4” in front of the face.