INSTALLATION MANUAL

9

2.1. RS-232 (Interactive & Block modes)

Interactive and Block modes support the 3-wire RS-232 configuration with TXD, RXD and signal common. The cable requires an overall shield to protect against electrical noise. Xon and Xoff can be used for communication handshaking.

 

3-Wire RS-232

 

 

 

Host Controller

 

MAP450D Terminal Block

 

 

 

 

TXD

 

Pin 9 ￿

RXD

 

 

 

 

RXD

 

Pin 10 ￿

TXD

 

 

 

 

Signal Ground

 

Pin 8 ￿

Return

 

 

 

 

2.2. RS-422/485 (Interactive & Block modes)

Interactive and Block modes support the 3-wire and 5-wire RS-422/485 configurations. The 3-wire configuration has both transmit and receive on the same pair of wires plus a signal common. The 5-wire configuration has differential signal pairs for transmit and receive plus a signal common. In both configurations the signal pairs must be twisted and surrounded by an overall shield.

NOTE: When using 3-wire RS-422/485, Jumper JP4 must be in position “B”. Refer to section 2.4 for instructions.

3-Wire RS-422/485

Host Controller

MAP450D Terminal Block

 

 

 

TXD+ & RXD+

Pins 4 & 6 ￿

RXD+ & TXD+

 

 

 

TXD- & RXD-

Pins 5 & 7 ￿

RXD- & TXD-

 

 

 

Signal Ground

Pin 8 ￿

Return

 

 

 

5-Wire RS-422/485

 

 

Host Controller

MAP450D Terminal Block

 

 

 

TXD+

Pin 4 ￿

RXD+

 

 

 

TXD-

Pin 5 ￿

RXD-

 

 

 

RXD+

Pin 6 ￿

TXD+

 

 

 

RXD-

Pin 7 ￿

TXD-

 

 

 

Signal Ground

Pin 8 ￿

Return

 

 

 

 

1010-0046A, REV 00

Page 9
Image 9