WARNING

HIGH VOLTAGES MAY BE PRESENT AT THE GENERATOR’S TERMINALS WHEN THE UNIT IS RUNNING. SOME ACCESSORY EQUIPMENT SUCH AS SPACE HEATERS MAY BE ENERGIZED FROM AN OUTSIDE POWER SOURCE WHEN THE UNIT IS AT REST. TOOLS, EQUIPMENT, CLOTHING AND YOUR BODY MUST BE KEPT CLEAR OF ROTATING PARTS AND ELECTRICAL CONNECTIONS. SPECIAL PRECAUTIONS MUST BE TAKEN DURING TROUBLESHOOTING SINCE PROTECTIVE COVERS AND SAFETY DEVICES MAY BE REMOVED OR DISABLED TO GAIN ACCESS AND PERFORM TESTS. BE CAREFUL. SERIOUS PERSONAL INJURY OR DEATH CAN RESULT FROM THESE HAZARDS. CONSULT QUALIFIED PERSONNEL WITH ANY QUESTIONS.

GENERATOR PRODUCES NO VOLTAGE

CAUSE

CHECK AND REMEDY

Voltmeter off or defective

Check voltage with a separate meter at the generator terminals.

Incorrect or defective connections

Verify generator connections. See drawings supplied with the generator or lead

 

connection diagrams in this manual. Inspect all wiring for loose connections, open

 

circuits, grounds, and short circuits.

Loss of residual

Flash the field. Refer to field flashing in the service section. If the generator is equipped

 

with a PMG, field flashing is not necessary -- check regulator fuse and input power from

 

the PMG.

Defective diodes, suppressor, or

Test the generator using the 12 volt battery test as specified in the testing section. If the

windings

results indicate generator problems, perform insulation, continuity, and diode tests as

 

specified in the testing section.

Regulator protection operating

Adjust regulator. Consult regulator manual.

Regulator inoperative

Adjust or replace regulator. Consult regulator manual.

GENERATOR PRODUCES LOW VOLTAGE, NO LOAD

CAUSE

Underspeed operation Voltmeter off or defective Incorrect or defective connections

CHECK AND REMEDY

Check speed using a tachometer or frequency meter.

Check voltage with a separate meter at the generator terminals.

Verify generator connections. See drawings supplied with the generator or lead connection diagrams in this manual. Inspect all wiring for grounds, open circuits and short circuits.

Loss of regulator power

Check regulator fuse and input power. Input power is produced by the generator’s

 

residual voltage or from an optional PMG.

Regulator adjustment

Adjust regulator settings. Consult regulator manual.

Regulator incorrectly connected

Review the generator connection diagram or reference the regulator manual.

Defective diodes, suppressor, or

Test the generator using the 12 volt battery test as specified in the testing section. If the

windings

results indicate generator problems, perform insulation, continuity, and diode tests as

 

specified in the testing section.

Regulator inoperative

Adjust or replace regulator. Consult regulator manual.

17

Page 42
Image 42
Baldor BALDOR GENERATORS, TS25, TS45, TS80, TS175 manual Generator Produces no Voltage, Generator Produces LOW VOLTAGE, no Load